6. INSTALLATION
In order to carry out the installation of the wallbox, the regulations and
requirements defined in the REBT and especially ITC-BT-52 must be followed.
It is recommended to have a value of the earth resistance lower than 100Ω
(Requirement for many electric vehicles) and in case of having a higher value,
corrective measures must be taken in the installation to reduce it.
The voltage value between neutral and earth must be around 0V with a value that
is recommended to be lower than 1V. The voltage between phase and neutral and
the other phases in a three-phase connection must be as balanced as possible and
the voltage drop must be under 5%.
The charging box will be fixed to the wall so that the lower part of the connector
is located at a height of between 0.9 and 1.2 m above the ground, according to
the United Nations Recommendation for Accessibility for the Disabled.
The fixing screws (not included) must have M6 threads, a minimum length of
50mm and with ridged or rounded cylindrical heads no greater than 12.5mm.
A support accessory for the charging hose is provided, which must be installed
next to the charging wallbox. The dimensions and the template for fixing the
accessory to the wall are defined below:
It is mandatory to install an independent filter for the wallbox (to be located
externally) and it is recommended the use of the EMIKON filter CMK4036 or
equivalent with the following characteristics:
Operating Voltage:
Three-phase 4 x 520 / 300VAC
Operation frequency:
DC to 60Hz
Rated Current:
36A
High potencial test voltage:
P->E2750VDC for 2 sec
P -> E2250VDC for 2 sec
Reliability:
MTBF 220.000 @ 50ºC
Overload:
4 times rated current at switch on, then
1.5 times rated current for 1 minute, once
per hour.
Climatic category:
-25ºC to +100ºC
Leakage current:
Max. Cable Entry:
10mm2
Power Loss:
14,8W
0,1 mA (Nom.)
7. POWER CONNECTION AND BUS (optional)
1. Mount (with threaded screws) the cable glands at the lower and/or upper part
of the charging box, as necessary.
2. Open the front cover of the charging solution with Torx TX25H key and tilt cover
with its hinges until in a position perpendicular to the mounting plane of the
charging solution.
3. Pass the wires through the lower and/or upper gland and located the Power
and BUS connection block.
4. Connect the power cables (single or three-phase) and BUS (optional) to the
charging box terminal block and close the front cover of the charging box once
all parameters have been checked. The cables must guarantee temperatures
of at least 100ºC and the use of at least 10mm2 cable section is recommended
in the case of three-phase power supply.
8. ELECTRONIC CHARGE CONTROL SETTINGS
To access the Electronics, you must lift the plastic visor in the upper front,
unscrewing the access screw.