3.2 BEFORE START UP

Before starting the machine, make sure that all operating parameters correspond to the nominal data.
The dryer is supplied already tested and preset for normal operation, and it doesn't require any calibration.
Nevertheless, it's necessary to check the operating performances during the first working hours.

3.3 START UP

The operations specified below must be performed after the first start up and at each start up after a
prolonged inactive period of time due to maintenance operations, or any other reason.
1. Make sure that all instructions contained in chapters INSTALLATION SITE and INSTALLATION
have been respected.
2. Check if by-pass is locked properly (if existent).
3. Activate current supply and press the ON/OFF switch on the control panel for at least 1 second.
Only on Mod. 400 ÷ 600
- Turn main power switch on position 1.
- Wait for 8 hours before starting the dryer
(the warranty is not valid if this procedure is not respected).
4. Wait 5 to 10 minutes until machine has achieved its standard operating parameters.
5. Slowly open the air outlet valve and successively open the air inlet valve.
6. If existent, close the by-pass.
7. Check if the condensate drainer is working properly.
8. Check if all connecting pipes are properly tightened and fixed.
Before disconnecting the dryer from electrical power supply, use ON/OFF key to stop the dryer.
Otherwise wait 10 minutes before switching the dryer on again, in order to allow freon pressure re-
balance.

4. MAINTENANCE, TROUBLESHOOTING AND DISMANTLING

4.1 MAINTENANCE

Before attempting any maintenance operation, make sure that:
1. No parts of the system is under pressure.
2. No parts of the system is electrically powered.
WEEKLY OR EVERY 40 HOURS OF OPERATION
Verify the temperature on the control panel display.
visually check if the condensate is drained regularly.
MONTHLY OR EVERY 200 HOURS OF OPERATION
Clean the condenser with a compressed air jet, taking care not to damage the cooling battery
aluminium wings.
At the end of the above mentioned operations, check if the dryer is working properly.
YEARLY OR EVERY 2000 HOURS OF OPERATION
Check if the flexible tube used for condensate drainage is damaged and replace it if necessary.
Check if all connecting pipes are properly tightened and fixed.
At the end of the above mentioned operations, check if the dryer is working properly.
EVERY 24 MONTHS OR EVERY 4000 HOURS OF OPERATION (Mod. 400 ÷ 600)
Replace the fan pressure switch.

4.2 TROUBLESHOOTING

NOTE: FOLLOWING BEHAVIORS ARE NORMAL CHARACTERISTIC OF OPERATION AND NOT TROUBLES
(ONLY FOR Mod. 10 ÷ 320):
• Variable speed of the fan.
• Visualization of message ESA in case of operation without load.
• Visualization of negatives values in case of operation without load.
Cod. 710.0138.20.00 Rev1A – 10.2010
ENGLISH
9 - 46