Associated outputs
If required, select other control outputs associated to the zone. The address zone will be the one with a lower value.
Other settings
Configure other functionalities of the LITE thermostat from the advanced configuration menu of a Blueface thermostat
ES
(see section Advanced Settings, Zone parameters).
EN
If the association is correct, the icon
flashes red twice, it means the thermostat is out of range.
FR
Remember: If you need to change the zone number, reset the thermostat and start association process.
IT

Lite thermostat reset

If you want to return your Lite thermostat to factory values, pull down all the microswitchs and reinsert the thermostat in its
PT
base. Press on
, the icon will flash green twice when the reset process is completed.
DE

INITIAL CONFIGURATION EVALUATION

Check the following aspects:
-
AC unit-system communication: Choose any mode (except STOP mode) and switch on the zone to generate demand.
-
Opening-closing of the dampers and control outputs: Turn on the system and generate demand in all the zones. Then,
switch off and on all the zones to verify the associated control outputs are correct.
Remember: For security reasons, the last zones takes 4 minutes to close.

FLOW REGULATION

Important: Start adjusting the flow from the central dampers and finish off with damper 1.

FLOW ADJUSTMENT (REG)

1.
Turn on and generate demand in all zones to open all the dampers.
2.
Turn off the zone/damper to be adjusted.
3.
Adjust the maximum opening you want with the REG lever (I/II/III/IV)
4.
Turn on the zone and check the flow is correct.
42
will flash green 5 times. If it flashes red, it means the zone is already occupied. If it