U
C
SER
ONFIGURABLE
F
UNCTION
Automatic Self-Test
UPS ID
Date of Last Battery Replacement
Minimum Capacity Before Return
from Shutdown
Alarm Delay After
Line Failure
Shutdown Delay
Duration of
Low Battery Warning.
Synchronized Turn-on Delay
High Bypass Point
Low Bypass Point
Output Voltage
Output Frequency
Number of Battery Packs
I
TEMS
N
: S
OTE
ETTINGS ARE MADE THROUGH SUPPLIED
N
M
OPTIONAL
ETWORK
F
ACTORY
D
EFAULT
Every 14 days
(336 hours)
UPS_IDEN
Manufacture Date
0 percent
5 second delay
20 seconds
2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately two
minutes of battery
runtime remains.
0 seconds
+10% of
output voltage
setting
-30% of output
voltage setting
208/230 V models:
230 VAC
Automatic
50 ± 3 Hz or
60 ± 3 Hz
1
6
P
C
OWER
,
T
ANAGEMENT CARDS
OR
ERMINAL
U
S
SER
ELECTABLE
C
HOICES
Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test
Up to eight characters to
define the UPS
mm/dd/yy
0, 15, 25, 35, 50, 60, 75,
90 percent
5 second delay,
30 second delay,
At Low Battery,
Never
0, 20, 60, 120, 240, 480,
720, 960 seconds
2, 5, 7, 10, 12, 15, 18,
20 minutes.
0, 20, 60, 120, 240, 480,
720, 960 seconds
+5%, +10%, +15%,
+20%
-15%, -20%, -25%, -30%
208/230 V models:
200, 208, 220,
230, 240 VAC
50 ± 3 Hz,
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz
Number of Connected
Batteries (four battery
modules per pack)
,
HUTE SOFTWARE
M
.
ODE
D
ESCRIPTION
Set the interval at which the UPS will execute
a self-test.
Uniquely identify the UPS, (i.e. server name
or location) for network management
purposes.
Reset this date when you replace the battery
modules.
Specify the percentage to which batteries will
be charged following a low-battery shutdown
before powering connected equipment.
Mute ongoing alarms or disable all alarms
permanently.
Set the interval between the time when the
UPS receives a shutdown command and the
actual shutdown.
The low battery warning beeps become
continuous when two minutes of runtime
remains.
Change the warning interval to a higher setting
if the operating system requires a longer
interval for shutdown.
Specify the time the UPS will wait after the
return of utility power before turn-on (to avoid
branch circuit overloads).
Maximum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
Minimum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
Allows the user to select the UPS output
voltage while online.
Sets the allowable UPS output frequency.
Whenever possible, the output frequency
tracks the input frequency.
Defines the number of connected battery packs
for proper runtime prediction.