SW 5: Setting LEDs
On: Enables both LEDs on the detector at all times (factory
default).
Off: Puts both LEDs under the control of the Walk Test and
Day/Night input. This activates the memory feature of the
detector.
LED indication
PIR
Red LED
Alarm relay
Start up
Closed
Low voltage
Open (Alarm)
PIR intruder
Open (Alarm)
alarm
PIR/AM
Red
Yellow
LED
LED
Start up
Low voltage
PIR intruder
alarm
Latched PIR
(Memory)
AM alarm
After AM reset
Technical fault
Continuously on
Normal blinking (1 Hz)
Fast blinking (4 Hz)
* Depends on the setting of the DIP switch SW4.
Specifications
Detector
Signal processing
Range
Optical
Memory
Input power
For UL installations
Peak-to-peak ripple
Detector start-up time
Normal current
For UL installations
Current in Alarm
Maximum current
(LED on)
Mounting height
Target speed range
Alarm (NC) / Tamper relay
characteristic
P/N 146251999-4 (ML) • REV D • ISS 12MAR13
To reset
Automatically after 25 s
Apply correct voltage
Automatically after 3 s
Alarm
AM
To reset
relay
relay
Closed
Closed
Automatically
after 60 s
Open
Open
Apply correct
(Alarm)
(Alarm)
voltage
Open
Automatically
(Alarm)
after 3 s
Switch to Night
mode
Open*
Open
See DIP
(Alarm)
(Alarm)
switch 3
Switch to
Night mode
Open
Do a successful
(Alarm)
walk test
EV1116
EV1116AM
PIR
PIR + AM
DSP
16 m
11 high-density mirror curtains
Yes
9 to 15 VDC (12 V nominal)
10 to 15 VDC (12 V nominal)
2 V (at 12 VDC)
25 s
60 s
5.5 mA
10 mA
0.0528 mW
—
2.5 mA
3.8 mA
11.5 mA
24 mA
1.8 m to 3.0 m (5.9 ft. to 9.8 ft.)
30 cm/s to 3 m/s
20 cm/s to 3 m/s
(1 ft./s to 10 ft./s)
(0.65 ft./s to
10 ft./s)
80 mA 30 VDC, resistive
Pry-off tamper (not
evaluated by UL/cUL)
AM relay characteristic
PIR alarm time
Operating temperature
For UL installations
Dimensions (H x W x D)
Relative humidity
Weight
IP/IK rating
Regulatory information
Manufacturer
UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943, USA
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, The Netherlands
Certification
UL
The product must be connected to a listed burglar
system compatible control unit or power supply unit,
which provides a minimum 4 hours of standby power
and has a voltage output between 10 and 15 VDC.
All wiring must be made according to National
Electrical Code, NFPA70, and CSA C22.1, Canadian
Electrical Code Part I, Safety Standards for Electrical
Installations.
Perform walk test at least one per year.
Use only a listed power-limited supply.
EV1116AM has not been evaluated by UL.
FCC
Note:
This equipment has been tested and found to
comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against
harmful interference in a residential installation. This
equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful
interference to radio communications. However, there
is no guarantee that interference will not occur in a
particular installation. If this equipment does cause
harmful interference to radio or television reception,
which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•
Reorient or relocate the receiving antenna
•
Increase the separation between the equipment
and receiver
•
Connect the equipment into an outlet on a circuit
different from that to which the receiver is
connected
•
Consult the dealer or an experienced radio/TV
technician for help
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2) this device must accept any interference
received, including interference that may cause
undesired operation.
EV1116
EV1116AM
Optional
On-board (Yes)
—
80 mA at 30 VDC
max., resistive
3 s
−10 to +55°C (14 to 130°F)
0 to 49°C (32 to 120°F)
125 × 55 × 60 mm
125 × 65 × 60 mm
(4.92 x 2.16 x
(4.92 x 2.6 x
2.36 in.)
2.36 in.)
95% max. noncondencing
(UL Installations)
150 g
IP30 IK02
5 / 32