WIRING INSTRUCTIONS

The Module can be connected to the Conventional Zone or Loop circuit by means of a standard two
wire connection (see Fig. 4, 5 and 6).
The MCP900/*Y version does not require an EOL Resistor.
It is possible to change the Alarm Resistance (RA) of the MCP900/*CS versions, from
270 Ω Ω Ω Ω Ω to 470 Ω Ω Ω Ω Ω , by cutting the jumper (see Fig. 3 and 5)
INSTALLATION GUIDELINES
Work carefully through the following steps (refer to Fig. 1):
1. Pull the connection wires through the wire entry of the outlet box or MCP900/*B back box.
2. Complete the Loop circuit or Conventional zone connections on the terminal board.
3. Select the required Address (for MCP900/*Y version only).
4. Remove the Front Face then stick the Lexan to the Operating Face.
5. Reassemble the parts.
If the MCP900 is to be flush mounted to an Italian standard 503 outlet box, it will be
necessary to fit an MCP900/*F flange (accessory item).
Code
MCP900/*S
Manual Call Point with Free Voltage Changeover Contact
MCP900/*CS Conventional Manual Call Point with Alarm LED and choice serie resistor
MCP900/*CB Conventional Manual Call Point with Status LED (for Alarm and Standby signalling)
MCP900/*Y
Addressable Manual Call Point (with System Sensor module)
MCP900/LI
Manual Call Point Lexan in Italian (10 piece kit)
MCP900/LS
Manual Call Point Lexan in Spanish (10 piece kit)
MCP900/LN
Manual Call Point Universal Lexan (10 piece kit)
MCP900/*F
Manual Call Point Flange (10 piece kit)
MCP900/*K
Manual Call Point key (10 piece kit)
MCP900/DN
Universal Security protection (10 piece kit)
N. B. - Bentel Security S.r.l. reserves the right to change the technical specifications of this product without prior notice.
PRODUCT VERSIONS AND ACCESSORY ITEMS