PR 9116 Manual Del Usuario página 36

Convertidor universal
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

LERBAKKEN 10, 8410 ROENDE DENMARK
Module 9116B1
Terminal 51-52, 51-53
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 μH
Module 9116B1
Group
Terminal 51-54, 52-54
Uo
28 V
Io
93 mA
Po
650 mW
Module 9116B1
Group
Terminal 51-53
Uo
28 V
Io
1.1 mA
Po
8 mW
Module 9116B1
Group
Terminal 51-52
Uo
8.3 V
Io
0.2 mA
Po
0.4 mW
Module 9116B1
Group
Terminal 41,42,43,44
Uo
8.3 V
Io
13.1 mA
Po
27.3 mW
Installation notes:
For group I (mines), the parameters for group IIA apply.
Install in pollution degree 2, overvoltage category II as defined in IEC60664-1
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n
or Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking
elements shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
Revision date:
2012-07-04
34
Co
Lo
Lo/Ro
IIC
80 nF
4 mH
54 μH/Ω
IIB
640 nF
16 mH 218 μH/Ω
2.1 μF
32 mH 436 μH/Ω
IIA
Co
Lo
Lo/Ro
IIC
80 nF 1000 mH
4 mH/Ω
IIB
640 nF 1000 mH 17 mH/Ω
IIA
2.1 μF 1000 mH 35 mH/Ω
Co
Lo
Lo/Ro
IIC
7 μF 1000 mH 100 mH/Ω
IIB
73 μF 1000 mH 400 mH/Ω
IIA
1000 μF 1000 mH 800 mH/Ω
Co
Lo
Lo/Ro
IIC
7 μF
207 mH
1 mH/Ω
IIB
73 μF
828 mH
5 mH/Ω
IIA
1000 μF 1000 mH 10 mH/Ω
Version Revision
V6 R0
9116 - Product Version 9116-003
Module 9116B2
Terminal 51-52, 51-53
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
1 μH
Module 9116B2
Group
Terminal 51-54, 52-54
Uo
21.4 V
IIC
Io
93 mA
IIB
Po
650 mW
IIA
Module 9116B2
Group
Terminal 51-53
Uo
21.4 V
IIC
Io
1.1 mA
IIB
Po
8 mW
IIA
Module 9116B2
Group
Terminal 51-52
Uo
8.3 V
IIC
Io
0.2 mA
IIB
Po
0.4 mW
IIA
Module 9116B2
Group
Terminal 41,42,43,44
Uo
8.3 V
IIC
Io
13.1 mA
IIB
Po
27.3 mW
IIA
Prepared by:
PB
9116QI01
Co
Lo
Lo/Ro
0.16 μF
4 mH
54 μH/Ω
1.13 μF
16 mH 218 μH/Ω
4.15 μF
32 mH 436 μH/Ω
Co
Lo
Lo/Ro
0.16 μF 1000 mH
4 mH/Ω
1.13 μF 1000 mH 17 mH/Ω
4.15 μF 1000 mH 35 mH/Ω
Co
Lo
Lo/Ro
7 μF 1000 mH 100 mH/Ω
73 μF 1000 mH 400 mH/Ω
1000 μF 1000 mH 800 mH/Ω
Co
Lo
Lo/Ro
7 μF
207 mH
1 mH/Ω
73 μF
828 mH
5 mH/Ω
1000 μF 1000 mH 10 mH/Ω
Page:
2/4

Publicidad