Approvals
Hazardous Locations
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups E, F, G
Class III
CLI, ZN1, AEx em II T*
Ex em ll T*
BR-Ex em II
E-100-LR is IECEx certified for use with:
BTV-CR/BTV-CT:
QTVR-CT:
XTV-CT:
KTV-CT:
VPL-CT:
(1)
Except VPL
*For system Temperature Code, see heating cable or design documentation
Kit Contents
Item Qty
Description
A
1
Light assembly
B
1
Core sealer (for BTV, QTVR, XTV, and KTV)
C
2
Insulated butt splices (red)
D
2
Insulated parallel crimps (blue)
E
1
Cable tie
WARNING:
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings
and carefully follow all of the installation instructions.
•
To minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of Tyco
Thermal Controls, agency certifications, and the National
Electrical Code, ground-fault equipment protection must
be used. Arcing may not be stopped by conventional
circuit breakers.
•
Component approvals and performance are based on
the use of Tyco Thermal Controls-specified parts only.
Do not use substitute parts or vinyl electrical tape.
(1)
IECEx BAS 06.0043X
IECEx BAS 06.0045X
IECEx BAS 06.0044X
IECEx BAS 06.0046X
IECEx BAS 06.0048X
.
•
The black heating cable core and fibers are
conductive and can short. They must be properly
insulated and kept dry.
•
Damaged bus wires can overheat or short. Do not break
bus wire strands when scoring the jacket or core.
•
Keep components and heating cable ends dry before
and during installation.
•
Bus wires will short if they contact each other. Keep
bus wires separated.
•
Use only fire-resistant insulation materials, such as
fiberglass wrap or flame-retardant foam.
•
Leave these installation instructions with the user for
future use.
E-100-LR
Light Replacement and Retrofit Kit for
High-Profile End Seal
Installation Instructions
Description
The E-100-LR light kit is used to replace the light on an E-100-L
high-profile lighted end seal or to retrofit a light to an existing E-100-A
high-profile end seal.
This kit may be installed at temperatures as low as –40°F (–40°C). For
easier installation store above freezing until just before installation.
Two units are available:
E-100-LR1 for 100–120 V
E-100-LR2 for 200–277 V
Make sure voltage rating of light is the same as that of the heat-tracing circuit.
For technical support call Tyco Thermal Controls at (800) 545-6258.
Tools Required
• Wire cutters
• Utility knife
• Marker
• Panduit CT-100 crimp tool
or equivalent
A
E
CAUTION:
Health Hazard: Prolonged or repeated contact with the
sealant in the core sealer may cause skin irritation.
Wash hands thoroughly. Overheating or burning the
sealant will produce fumes that may cause polymer
fume fever. Avoid contamination of cigarettes
or tobacco. Consult MSDS VEN0033 for further
information.
CHEMTREC 24-hour emergency telephone:
(800) 424-9300.
Non-emergency health and safety information:
(800) 545-6258.
• Rags or dry towel
• Wire strippers
• Needle nose pliers
B
C
D