Single fan installation for Basic 6
Powerfoil
8 Plus fans
®
Parameter Changes ARE required
P101 "Standard Reference Source" must be changed from "0" for keypad operation to "2" for 4-20mA analog input
operation.
Basic 6
, Powerfoil
®
U/T1
16
8, or Powerfoil
®
VFD (cover removed)
1 2 5 6
1
2
5 6
25
25 4 11
4 11
13A 13B 13C 14 30 16 17
13A 13B 13C 14 30 16 17
PE
V/T2
W/T3
L1
L2
WWW.BIGASSSOLUTIONS.COM
, Powerfoil
®
8 Plus
®
L3
2 conductor shielded cable 18-22AWG Stranded
(provided by installer) Maximum distance >1000ft
Top of Wall Pad
SmartSense
Wall Controller
© 2015 DELTA T CORP.
ALL RIGHTS RESERVED.
8, and
®
Upper
Temperature
Sensor
Reserved
Reserved
Reserved
DC Common (Shield) (Gray)
4–20 mA Input from RTS (Black)
+24 VDC RTS Supply Out (Red)
4–20 mA Out to Fan Controller (Red)
DC Common (Shield) (Black)
+24 VDC Supply In (Gray w/ White)
DC Common (Shield) (Gray)