Descargar Imprimir esta página

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

WS Series Passive Infrared Occupancy/Vacancy Wall Switch Sensors
SPECIFICATIONS (WS2000, WS2004 models)
• 1200 sq. ft coverage area
• Electrical Ratings :
120VAC – 1000W Incandescent, 8.3A Ballast
277VAC – 6.5A Ballast
• Adjustable Time Delay: 30 seconds to 30 minutes
• Light Level Adjustment: 10 - 500+ fc
• Zero-Cross Switching Circuitry
• UL Listed
• Both Neutral and Ground wire versions available
• Auto/Manual ON Mode, Multi-Way function
SPECIFICATIONS (WS1000, WS1001 models)
• 1200 sq. ft coverage area
• Electrical Ratings:
120VAC – 600W Incandescent, 5A Ballast /CFL/LED, 1/6 H.P.
• Adjustable Time Delay: 6 seconds - 20 minutes
• UL Listed
• Vacancy (Manual ON) models available
PRECAUTIONS
CAUTION: RISK OF ELECTRICAL SHOCK. Turn power off at
service panel before beginning installation. Never wire energized
electrical components.
CAUTION: USE COPPER CONDUCTOR ONLY.
NOTICE: For indoor use only.
NOTICE: For installation by a licensed electrician in accordance with
National and/or local Electrical Codes and the following instructions.
NOTICE: Confirm that device ratings are suitable for application prior
to installation. Do not install if any damage to product is noticed.
INSTALLATION
1. Turn power off at the service panel.
2. (For new installation) Select a suitable location for the sensor.
Make sure the sensor will not be blocked by doors or other
obstacles. In addition, make sure the sensor will not detect motion
in adjacent areas or hallways causing the lights to turn on when
not desired. The sensor should have a line of sight view of the
occupant's hands for best performance. Note the area of coverage
diagram. Mount the sensor 42" to 54" (107-137 cm) from the floor.
(For existing switch installation, remove old switch and replace
with sensor.)
3. Wire the sensor(s) as shown in the wiring diagrams.
Connect BLACK wire to HOT or LINE conductor.
Connect WHITE wire to NEUTRAL conductor. (Neutral models only)
Connect RED wire to lighting LOAD conductor.
Connect GREEN wire to equipment grounding conductor, "GND".
(Green, Green/Yellow or Bare wire) Ground wire power sensors
must be securely connected to ground to operate.
For multi-way applications (WS2000xx), connect the YELLOW wires
from each sensor. Connect a RED wire from only one sensor to load.
Cap RED wire on other sensor.
4. Install sensor in wall box using mounting screws provided.
5. Restore power to the sensor and allow it to initialize (up to 45 sec).
6. If it is desired to change settings, remove the sensor's front button
cover and see time delay and daylight control settings.
7. Install wall plate.
Wiring Device-Kellems
40 Waterview Drive
Shelton, CT 06484
(800) 288-6000
www.hubbell-wiring.com
PD2547
Page 1
Hubbell Energy Efficiency Solutions
Installation and Operating Instructions
02/17
Top View / Vue en plan / Vista por encima
Major Motion / Mouvement fréquent / Movimiento frecuente
Minor Motion / Mouvement occasionnel / Movimiento ocasiona
Side View / Vue de côté / Vista lateral
Floor/Plancher/Piso
0' [m]
20' [6,1 m]
WS1001
WS1001N
12' [3,7 m]
16' [4,9 m]
40' [12,2 m]
WS2000
WS2000N
WS2004
WS2004N
WS1000
WS1000N
l
®

Publicidad

loading

Resumen de contenidos para Hubbell WS1001

  • Página 1 • Zero-Cross Switching Circuitry • UL Listed • Both Neutral and Ground wire versions available • Auto/Manual ON Mode, Multi-Way function SPECIFICATIONS (WS1000, WS1001 models) • 1200 sq. ft coverage area • Electrical Ratings: 120VAC – 600W Incandescent, 5A Ballast /CFL/LED, 1/6 H.P.
  • Página 2 Operation Time Delay Setting WS2000 series: Initially factory set to 15 minutes. Front press switch operation: (Vacancy Mode = Manual ON, WS1000 series: Initially factory set to 10 minutes. Occupancy Mode = Automatic ON) When the sensor is set to vacancy Remove wall plate and button cover on the front of the sensor.
  • Página 3 Capteurs WS • Mode Auto/ON manuel, fonction multidirectionnelle 1. Régler la temporisation (TIME) au minimum (complètement dans le sens SPÉCIFICATIONS (MODÈLES WS1000, WS1001) contraire des aiguilles d'une montre). (Consulter l'illustration Commandes). • Portée de 111 m² 2. Sortir du champ de vision du capteur (la DEL qui capte le mouvement arrêtera •...
  • Página 4 HUBBELL DE MEXICO garantiza este producto, de estar libre de defectos en materiales y mano de nuevamente. obra por un período de un año a partir de la fecha de su compra. HUBBELL reparará o reemplazará a Cuando se presiona el interruptor pulsador delantero en otro modo para encender su juicio el producto en un plazo de 60 días.

Este manual también es adecuado para:

Ws1001nWs2000Ws2000nWs2004Ws2004nWs1000 ... Mostrar todo