Abbreviation Meaning In Lcd Display - SHT 10K Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3) After it shuts down, you can turn off the battery breaker (for long-run model) and remove the
parallel and share current cables. And then remove the unit from the parallel system.
Second method:
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system first.
2) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs
will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance
switches from "UPS" to "BPS". Turn off all the input breakers and battery breakers in parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS which
you want to remove. Then, remove it from parallel system.
4) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set
the maintenance switches from "BPS" to "UPS and put the maintenance bypass covers back.
5) Turn on the remaining UPS according to the previous section.
Warning: (Only for the parallel system)
● Before turning on the parallel system to activate inverter, make sure that all unit's maintenance switch
at the same position.
● When parallel system is turned on to work through inverter, please do not operate the maintenance
switch of any unit.

3-6. Abbreviation Meaning in LCD Display

Abbreviation
Display content
ENA
DIS
ATO
BAT
NCF
CF
SUB
ADD
ON
OFF
FBD
OPN
RES
N.L
CHE
OP.V
PAR
AN
BN
Meaning
Enable
Disable
Auto
Battery
Normal mode (not CVCF mode)
CVCF mode
Subtract
Add
On
Off
Not allowed
Allow
Reserved
Neutral line loss
Check
Output voltage
Parallel, 001 means the first UPS
The first phase
The second phase
15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

10kl15k15kl20k20kl30k ... Mostrar todo

Tabla de contenido