Idiomas disponibles

4 - SETTINGS 3200 / 3210 /
3220 / 3230 TIMER
Rear view of the timer
2 microswitches:
- The lower one is for the
auto-on of the motor and the
service position of the timer.
- The upper one activates the
regeneration cycles.
Timer motors:
- 1/30 R.P.M.
- 1/15 R.P.M.
Meter cable
connector
Wheel setting
DOWNFLOW
1
Backwash
2
Brine draw and slow rinse
3
Rapid rinse
4
Brine refill
Always put these 2 pins
5
at the end of setting
The cycle times are factory set.
Each pin or hole equals 2 minutes or 1 minute with 1/15 R.P.M.
Motor
It is recommended to check if each cycle time is adapted to
the sites specific.
To modify the cycle time of each regeneration, place or
remove pins.
Example: drawing on the left:
1- Backwash: from 10 to 14 min
2- Brine draw and slow rinse: from 60 to 40 min
3- Rapid rinse: on from 10 to 6 min
4- Brine refill: from 20 to 12 min
15
UPFLOW
False cycle (2 pins)
Brine draw and slow rinse
(up flow)
Backwash
Rapid rinse
Brine refill
Regeneration cycle
programming wheel
Additional pins
Program label (82 or 164 min)
according to motor speed
- 2 min. per pin with the
1/30 R.P.M. motor
- 1 min. per pin with the
1/15 R.P.M. motor
3150 - 3900
E
N
G
L
I
S
H

Publicidad

loading

Este manual también es adecuado para:

3900Fleck 3150