In case you see an error code in the LED strip, please contact epic
power for assistance at support@epicpower.es, indicating the number
of errors that appear.
Disabled: In case ERS 2G is disabled by an external control signal LEDs
will turn ON one by one. Enabling and disabling of ERS 2G is explained
next.
6-way connector:
-
Terminals 1 and 2: External ENABLE signal. Isolated input.
ii)
Closed. A shortcut is created between terminals 1 and 2 by an
external source: ERS is ENABLED.
It is necessary that the elevator control is the one that generates
this enabling signal.
iii) Open: Drive supply is disabled. VVVF drive is not being energized by
our system. ERS is DISABLED but ready to be enabled. LEDS will
move from left to right and vice-versa in a quick mode to showcase
that the ERS is disabled but not turned-off.
-
Terminals 3 and 4: STATUS OK. Isolated output. Indication of the
system state
o
Short-circuit between terminals 3 and 4 (closed): The system (ERS
2G) is working correctly.
o
Open: The system (ERS 2G) is not working.
-
Terminals 5 and 6: RESERVED for other uses. .
Instalation guide
25