PROBLEM
THE DISPLAY SHOWS
C01
THE DISPLAY SHOWS
C05
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A30, A32, A33, A34
THE UPS WILL NOT
START UP
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F09, F10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F03, F04, F05, A08, A09,
A10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F42, F43, F44, L42, L43,
L44
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
POSSIBLE CAUSE
NO JUMPER ON R.E.P.O.
CONNECTOR (SEE "FRONT
UPS VIEWS") OR JUMPER
NOT INSERTED PROPERLY
MANUAL BYPASS SWITCH
(SWMB) CLOSED
NO JUMPER ON TERMINALS
FOR REMOTE MAINTENANCE
BYPASS (A3-A4, "UPS
CONNECTIONS VIEW")
AMBIENT
TEMPERATURE < 0°C
TEMPERATURE SENSOR
MALFUNCTION ON
DISSIPATOR
UPS INPUT STAGE
MALFUNCTION
PHASE 1 PRESENTS
VOLTAGE MUCH LOWER
THAN THE OTHER TWO
PHASES.
INSERTION OF ABNORMAL
LOADS
UPS INPUT OR OUTPUT
STAGE MALFUNCTION
NO CONNECTION ON ONE OR
MORE PHASES
FUSES BROKEN INSIDE
PROTECTIONS ON PHASES
OR INPUT CONTACTOR
FUSES BROKEN INSIDE
PROTECTIONS ON
BATTERIES
SOLUTION
Connect or properly insert jumper. If present, verify that
the
optional
emergency
information detailed in the R.E.P.O. paragraph
If the switch (SWMB) located behind the door was not
closed intentionally, open it
Insert the jumper or, if an additional auxiliary contact is
present, follow directions described in paragraph
"Remote Maintenance Bypass"
Heat up the room, wait for dissipater temperature to
exceed 0°C and start up the UPS
Activate manual bypass (SWMB), switch off the UPS,
re-start the UPS and exclude manual bypass. Call the
nearest service centre if this problem persists.
Activate manual bypass (SWMB), switch off and re-start
the UPS. Exclude manual bypass Contact the nearest
service centre if this problem persists
Open the SWIN, switch on batteries, wait for sequence
completion and close the SWIN
Remove load. Insert manual bypass (SWMB), switch off
and re-start the UPS. Exclude manual bypass Call the
nearest service centre if this problem persists.
Activate manual bypass (SWMB), switch off and re-start
the UPS. Exclude manual bypass Contact the nearest
service centre if this problem persists
Verify terminal connections
Call the nearest service centre
Call the nearest service centre
contact
complies
with
Pag. 102 di 272 + FR