Peco TW205 Instrucciones De Instalación

Ocultar thumbs Ver también para TW205:

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

CAUTION
!
• Use copper wire only, insulate or wire nut all unused leads.
• Care should be used to avoid electrostatic discharge to the thermostat.
THE PECO WAVE WIRELESS SYSTEM™
The PECO Wave Wireless System is comprised of the TW205 or TW206 wireless thermostat
paired with a RW205 receiver. Optional accessories to the system are the SW205 wireless
occupancy sensor and SW206 wireless door switch.
The TW205 thermostat is a nonprogrammable digital thermostat that may be powered by
battery, 24 VAC, or both. It features separate heating and cooling setpoints, auto changeover,
fan control functions, and wireless communication with the RW205 receiver. The RW205
receiver is wired to the HVAC equipment and controls all outputs. The optional SW205
occupancy sensor and SW206 door switch also communicate wirelessly with the RW205
receiver to signal occupancy status.
The TW206 thermostat is the programmable model. It includes all the features of the TW205
thermostat plus 7-day programming, four time periods per day, and hold/override options.
APPLICATIONS AND FEATURES
The PECO Wave Wireless System is intended for use in PTAC, PTHP, and On/Off control
applications.
• System mode selections: Off-Heat-Cool-Auto-Setback
• Stages: 1 Heat/1 Cool, 2 Heat/1 Cool, 1 Heat/2 Cool
• 6 outputs (RW205): 1 Heat, 1 Cool, Up to 3 Fan, Outside Air Damper / Reversing Valve
• Fan control: 1-3 Speeds, Cycling (Auto) or Continuous (On)
• Permanent memory: The thermostat does not need batteries to store user-confi gured
settings in memory. Nonvolatile memory (EEPROM) saves temperature setpoints, fan, and
system settings for unlimited time. In the event of power loss, time settings are kept for at
least one year (TW206).
• Connections for Remote Temperature Probe and Setback (RW205)
FRONT PANEL REFERENCE
Liquid crystal display
with blue blacklight
System button
Fan button
Device connection
indicator lights
Connect button
(use paperclip
tip to depress)
© COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED.
TW205-206 WIRELESS THERMOSTAT
Aux
AUTO
OFF
HEAT
Up/ down buttons
COOL
FAN
SETBACK
Auto ON
Fahrenheit/ Celsius
temperature display
F/C
F/C
button (TW205) or
Program button
(TW206)
TW205 Thermostat
RW205 Receiver
INSTALLATION INSTRUCTIONS
!
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
Failure to observe safety information and comply with instructions could result
in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before
installing or servicing and use only wiring with insulation rated for full thermostat
operating voltage.
Before installing this control, the Voltage Selection Switch must be placed in the
correct position. See instructions.
To avoid potential fi re and/or explosion do not use in potentially fl ammable or
explosive atmospheres.
Retain these instructions for future reference. This product, when installed,
will be part of an engineered system whose specifi cations and performance
characteristics are not designed or controlled by PECO. You must review your
application and national and local codes to assure that your installation will be
functional and safe.
SPECIFICATIONS
Temperature Range:
Differential:
Input Power:
Input Power (cont.):
Wireless Type:
Wireless Range:
Operating Temperature:
Shipping Temperature:
Operating Humidity:
Physical Dimensions:
WAVE WIRELESS SYSTEM MOUNTING CONSIDERATIONS
When selecting mounting locations for Wave Wireless System components, it is important
to consider the number and types of obstructions between components. The Wave Wireless
System will communicate through walls and other obstructions but they will reduce the
effective operating range of these devices. Mounting any device within a metal enclosure
may signifi cantly reduce its communicating range. The Wave Wireless System uses
Frequency Hopping technology to improve its resistance to wireless interference; however,
malfunctioning or improperly used wireless devices may interfere with the Wave Wireless
System. Take note of any other wireless devices in use near the Wave Wireless System
before installation or if communication errors occur frequently.
INSTALLATION
STEP 1 OF 4: THERMOSTAT WIRING AND MOUNTING
Mounting Location
The thermostat should be used indoors only. It should be mounted on an inner wall in
a location with freely circulating air, and where it will be responsive to changes in room
temperature. Avoid mounting near heat generating appliances (i.e. TV, heater, refrigerator),
or in direct sunlight.
Power Options
The thermostat will operate on either 24 VAC power or two AA alkaline batteries. Follow
instructions for chosen power option in the appropriate section below. If desired, thermostat
may operate on 24 VAC power with battery backup (follow the 24 VAC Power instructions).
WARNING
50° to 90°F (10° to 32°C)
1°F (0.5°C)
TW205 / TW206 thermostat: Two AA alkaline
batteries or 24 VAC, 50/60 Hz
RW205 receiver: 24 VAC or 100-277 VAC, 50/60 Hz
902 to 928 MHz Band, FHSS
(Frequency Hopping Spread Spectrum)
100 ft minimum in open air
0° to 120°F (-17° to 48°C)
-20° to 130°F (-28° to 54°C)
5% to 95% RH, non-condensing
TW205 / TW206: 4.5"H x 5.75"W x 1.1"D
RW205: 4.8"H x 3.8"W x 1.3"D
P/N 69512 3220-3139 REV 0 PAGE 1

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Peco TW205

  • Página 1 PECO. You must review your The TW206 thermostat is the programmable model. It includes all the features of the TW205 application and national and local codes to assure that your installation will be thermostat plus 7-day programming, four time periods per day, and hold/override options.
  • Página 2 Disconnect the wires from the old thermostat one at a time. Do not let wires fall back NOTE: If you are installing more than one TW205 and RW205 set nearby each other, you into the wall.
  • Página 3 1-60 Minutes 25 Minutes Defi nes the duration in which fan will be off. Fan Off Time will be activated after Fan On Time has passed. © COPYRIGHT 2009 PECO, INC. ALL RIGHTS RESERVED. P/N 69512 3220-3139 REV 0 PAGE 3...
  • Página 4: Application Notes

    (In this case the OA/RV OUTPUT can be used to control and outside air damper.) cooling setback limits are used as temperature control points and fan operation is cycled with demand at the lowest speed. Pressing any button on the TW205/206 thermostat will Multi-Stage Systems override the setback for 1 hour.
  • Página 5 SETBACK Setback mode is an energy saving feature that minimizes the The following operating instructions are only for the TW205 nonprogrammable thermostat. heating and cooling when the room is not occupied. Setback mode Please refer to the “TW206 Owner’s Manual” for the operating instructions for the TW206 overrides the standard setpoints by telling the thermostat to instead use the setback setpoints for heating and cooling.
  • Página 6: Referencia Del Panel Delantero

    El termóstato TW206 es el modelo programable. Éste incluye todas las características del termóstato TW205 más la programación de 7 días, cuatro períodos de tiempo por día y opciones de anulación/espera. REFERENCIA DEL PANEL DELANTERO APLICACIONES Y CARACTERÍSTICAS...
  • Página 7: Instalación

    Asegúrese de pelar el aislamiento de cada cable a la longitud correcta e inserte los NOTA: Si está instalando más de un juego de TW205 y RW205 colocados uno cerca del cables en el bloque de terminales como se muestra en el diagrama de cableado: otro, debe aplicar la energía a un juego a la vez y después debe realizar el proceso de...
  • Página 8 Defi ne la duración en la que el ventilador estará apagado. El tiempo de apagado del ventilador se activará ventilador después de que haya transcurrido el tiempo de encendido del ventilador. © COPYRIGHT 2009 PECO, INC. TODOS LOS DERECHOS RESERVADOS. P/N 69512 3220-3139 REV 0 PÁGINA 8...
  • Página 9: Paso 4 De 4: Verifique El Funcionamiento Del Termóstato

    Si la comunicación • Si es necesario energizar la válvula de inversión con una demanda de calefacción, coloque se interrumpe por más de 5 minutos, en el caso del TW205/206 o 30 minutos para el el menú de servicio n.° en “1”.
  • Página 10 REAJUSTE El modo de reajuste es una característica de ahorro de energía que Las siguientes instrucciones de funcionamiento son sólo para el termóstato TW205 no minimiza la calefacción o el enfriamiento cuando no está ocupada la programable. Consulte el “Manual del propietario TW206” para obtener las instrucciones de habitación.
  • Página 11 Le non-respect des directives de sécurité et de se conformer aux instructions peut Le système sans fi l par onde de PECO comprend le thermostat sans fi l TW205 ou TW206 et entraîner des BLESSURES CORPORELLES, LA MORT ET/OU DES DOMMAGES un récepteur RW205.
  • Página 12 1. Installez le récepteur RW205 en suivant la procédure décrite dans le « Guide d’instructions a. Faites passer les fi ls à travers les trous de la plaque arrière des TW205/TW206. de l’installation du récepteur RW205 » fourni avec le RW205.
  • Página 13 Détermine la période pendant laquelle le ventilateur sera en arrêt. La période d’arrêt du ventilateur sera activée dès intermittent que le temps de marche du ventilateur sera écoulé. © COPYRIGHT 2009 PECO, INC. TOUS DROITS RÉSERVÉS. Réf. 69512 3220-3139 RÉV. 0 PAGE 13...
  • Página 14: Conformité Fcc

    • Réglez la fonction no 41 du menu à « 0 ». le système sans fi l de PECO avec des systèmes utilisant des SORTIE OA/VR pour le (Dans ce cas, la fonction OA/VR (air extérieur/robinet inverseur) peut servir à contrôler un chauffage et la climatisation.
  • Página 15 Les instructions d’utilisation suivantes s’appliquent seulement au thermostat non POINT DE d’économiser l’énergie et qui minimise le réchauffement et le programmable TW205. Veuillez vous référer au « Manuel d’utilisation du TW206 » pour CONSIGNE refroidissement quand la pièce est inoccupée. Le mode remise au les instructions sur le fonctionnement du thermostat programmable TW206.

Este manual también es adecuado para:

Tw206

Tabla de contenido