The Rapid Shutdown can be initialized by means of AC failure if the signal lines are con-
nected to the inverter. Alternatively or additionally, an emergency stop button that inter-
rupts the signal wires can be used.
System Limita-
-
tions
-
-
Maximum Dis-
tance Between
the Rapid Shut-
down Box and the
PV Array
Technical Data
Max. voltage
Start voltage
Max. input current
Power supply
Self-consumption during operation
Permissible operating temperature
Permissible humidity
Max. altitude
Maximum number of Rapid Shutdown Boxes per inverter: 5
Maximum line resistance permitted in the signal loop: 300
Maximum permissible wire length for signal loop using AWG 14, 16, 18 or 20: 3200ft
(1000m)
RSB Duo
RSB Quattro
600 V DC
80 V DC
25 A
25 A / 25 A
DC (from the PV array)
2 W
-40° F to +149° F (-40° C to +65° C)
0 - 100 % (not condensing)
13,123 ft. (4000 m)
7