Magnetic low-voltage dimmers: For more information, see Application Note 19: "Guide to Dimming Low-Voltage Lighting," P/N 048019, at www.lutron.com. Operation of a dimmed low-voltage
circuit with all lamps removed or inoperative may result in current flow in excess of normal levels. To avoid possible transformer failure, Lutron strongly recommends the following: Do not
operate dimmed low-voltage circuits without operative lamps in place; replace burned-out bulbs immediately; and use transformers that incorporate thermal protection or fused transformer
primary windings in order to prevent transformer failure caused by excess current.
•
Electronic low-voltage dimmers: These dimmers are overload-protected. If more than the rated load is applied, power to the circuit will shut off until the dimmer cools. If this happens, remove
excess load from the circuit.
•
For NTELV- models minimum load is 5 W.
•
Fan-Speed controls: Use with fans marked "Suitable for use with solid-state fan-speed controls only." Set multi-speed fans to their highest setting before installing controls.
•
Quiet fan-Speed controls: Do not wire into a circuit with a GFCI breaker or receptacle. Set multi-speed fans to their highest setting before installing controls. Not recommended for use with
Hunter Original Series fans; contact Customer Assistance for suitable controls.
•
For LED loads, please see the "Report Cards" at www.lutron.com/hilumeled for proper loading of the dimmer.