SPEEDMATIC ALT
CONFIGURATION.
By mean of
we can change the values and press ENTER for validation. Whenever we want to quit the configuration sequence
press MENU. After every ENTER it will appear automatically the different screens that constitute the sequence of configuration.
0
P LINE
SET P
0,0 bar
0,0 bar
1
LANGUAGE ENGLISH
2
SET UP MENU
3
MAX. INT. PUMP 1
OFF
4
MAX. INT. PUMP 2
OFF
5
ROTATION SENSE PUMP1
0
6
ROTATION SENSE PUMP2
0
7
MIN. SPEED
15 Hz
LEVEL PROBE
8
NO
9
PROGRAMMING MENU
10
SET PRESSURE
2,0 bar
11
DIF. START
0,3 bar
12
TIMER STOP
5 s
VIEW MODE
13
PRESSURE
14
P LINE
SET P
0,0 bar
0,0 bar
Hz
LINE
SET P
42
2,0 bar 2,0
REGISTER OF FUNCTIONS AND ALARMS
Pushing simultaneously MENU +
able to advance inside the register, once we get the last register we can go back to the main menu pushing ENTER again. The
visualization sequence is as follows:
P LINE
SET P
0,0 bar
0,0
P LINE
SET P
0,0 bar
0,0
5
To start configuration sequence push MENU during 3".
By mean of keys
we can choose the languages: "LANGUAGE ENGLISH", "LANGUE
FRANÇAISE", "LINGUA ITALIANA" e "IDIOMA ESPAÑOL".
Being inside configuration menu we are having access to the phase of installation.
By mean of keys
enter the nominal intensity value in A of pump 1 enabling the thermal protection. This
value is located over the characteristics plate of the motor. Press ENTER for validation.
Follow instructions of the previous step. See intensity value in A over the characteristics plate.
Using the START/STOP pushbutton corresponding pump 1 verify its rotation sense. By mean of keys
(0/1) we can change it. Press ENTER for validation.
0 Hz
This screen is not available if we have selected single-phase pumps.
Proceed identically for pump 2.
0 Hz
Using
we can increase the lower limit of the speed of rotation of the pump´s motors.
If the installation does not have level probe press ENTER to validate NOT. If the installation has a level probe,
by mean of keys
we can change NO by YES.
Being inside configuration menu we are having access to the phase of programming.
This will be the system working pressure. Use keys
WARNING! input pressure must be al less 1 bar lower than the maximum pressure of the pumps. Set
pressure must be under 12 bar.
The default value is 0,3 bar. This value of pressure is the one that the system will subtract to the input
pressure, resulting the final pressure to which the system will set in motion when the hydraulic network
have a demand. Using keys
between 0,3 and 0,6 bar. Example:
The value should be greater as much as smaller be the accumulation and vice versa.
"TIMER STOP" default value is 5". This will be the employed time by the system in stopping once ceased the
consumption in all the installation. Using keys
There are 2 view modes to choose::
- Pressure: it is visualized "P LINE" (real pressure of the installation) and "SET P" (working programmed
pressure).
- Service: it is visualized "Hz" (working frequency of the inverter), "LINE" (input pressure chosen), "SET P"
(real pressure of the installation) y "FL" (flow sensor state).
After pressing ENTER pushbutton, the system will remain configured showing the
type of view chosen in the previous section.
Press AUTOMATIC in order to quit manual mode.
FL
1
during 3" we will get the register of functions and alarms, by mean of the pushbutton ENTER we are
FUNCTION REGISTER
HOURS
26 h
MENU+
Register of operational controls
ALARM REGISTER
NO WATER
Register of alarms
for modify the initial value (2 bar).
to modify the initial value. It is recommended to maintain this value
- Input pressure:
- Differential start:
- Final start pressure:
we can modify the initial value.
FUNCTION REGISTER
ENTER
ENTER
STARTS
32
ALARM REGISTER
ENTER
ENTER
I MAX. P2
0
2
bar.
0,3 bar.
2 - 0,3 =
1,7 bar.
AUTOMATIC
FUNCTION REGISTER
ENTER
CONNECTIONS
25
ALARM REGISTER
ENTER
TEMP.
0
EN
MENU
3"
ENTER
ENTER
3"
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ALARM REGISTER
SHORTCIRC.
0
ENTER
ALARM REGISTER
I MAX P1
0