2.
Securely fasten enclosure to the mounting location, then attach
into conduit system.
3.
If remote indicating systems are used, be sure they comply with
NEC requirements, ensure grounding continuity, and are within
electrical ratings listed on the Field Wiring Diagram.
Hammers or prying tools must not be allowed to damage the
flat ground-joint surfaces or cover gasket.
Clean both ground-joint surfaces of body and cover before
closing. Dirt or foreign material must not accumulate on flat
ground-joint surfaces. Surfaces must seat fully against each
other to provide a proper explosionproof seal.
4.
Open cover for access to terminal block. Attach field wiring to
terminal block and to additional green ground lug, following the
wiring pattern established for your system and the Field Wiring
information contained in this instruction sheet.
5.
Check wiring for correctness with continuity tester and for
unwanted grounds with insulation resistance tester.
6.
Close cover and tighten all cover bolts, torque to 15-20 ft. lbs.
(20.3-27.1 Nm).
Make sure wire casing is safely tucked into enclosure before
closing EGL cover.
CAUTION:
AVOID DAMAGE WHILE CLOSING COVER.
PRIMARY
VOLTAGE
460
230
IF 1512 • 11/11
CAUTION
CAUTION
WARNING
SUFFIX
S883 ONLY
SUFFIX
R11 ONLY
HEATER
TRANSFMR
WHITE
BLACK
ARRANGE WIRES TO
LINE 1
LINE 2
CONNECTION
CONNECT
CONNECTION
#2
#1 & #4
#3
#1 & #2
#3 & #4
EGL210 GROUND INDICATOR FIELD WIRING
FIGURE 2 - WIRING DIAGRAM
Copyright © 2011, Cooper Industries, Inc.
Before assembling any mating threads, make certain that
there is no dirt or other foreign material on, or in, either set
of threads.
Conduit(s), and any plug(s) threads must be engaged
properly with their mating threads and securely tightened.
All threaded joints in the enclosure have been treated at the
factory with Crouse-Hinds STL screw thread lubricant which
acts as a lubricant and anti-seize agent. Whenever any
threaded joint(s) are disassembled, the threads should be
re-treated with STL and care must be exercised in mating
threads properly, and securely tightening the threaded
joints.
NOTES:
1.
For standard 120V supply voltage, connect leads directly to
terminals: "1" for power, "2" for neutral, "3" for ground. The
additional ground wire must be attached to the green wire lug,
which is factory installed in the enclosure. For 240 or 480 volt
control voltages connect leads directly to the transformer as
marked.
2.
Terminals 4, 5, 6, 7, 8, and 9 on the terminal block are
connected to the control relay's contacts and are to be used for
connections to remote indicators or control circuits. The
electrical ratings for the relay's contacts are given on the field
wiring diagram. Terminals 4 & 5 and 7 & 8 are normally open.
Terminals 4 & 6 and 7 & 9 are normally closed.
WIRING DIAGRAM - EGL210
BLK
1
2
WHT
WHT
MTL 5018AC
WHT
3
BLK
WHT
GRY
BLK
3
4
5
6
7
1
2
2
GRY
YEL
4
2
RELAY
COIL
BLU
1
3
BLK
CAUTION
S4
BLK
9
BLK
7
12
BLK
10
RED
BLK
13
8
14
11
SUFFIX
J1, J3 ONLY
BLK
WHT
PUR
8
9
BRN
6
8
5
7
RED
ORG
OFF
ON
OFF
OFF
WHT
G
WHT
R
LED'S
Page 2