- the package contains the product fitted with a pull-out terminal block, - operating instructions. PreSenTaTiOn DIRIS A20 are multifunction meters which make available to the user, all the necessary steps in order to carry out energy efficiency projects and monitor the electrical distribution.
DIRIS A20 inSTallaTiOn reCOmmenDaTiOnS • Avoid proximity to systems which generate electromagnetic interference. • Avoid vibrations with accelerations in excess of 1 g for frequencies below 60 Hz. CUT-OUT Diagram mOUnTing DIRIS A20 - Ref.: 538848 A...
120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC OPTiOnal mODUleS The DIRIS A20 can be fitted with optional modules: • JBUS/MODBUS communication (ref: 48250082) RS485 JBUS/MODBUS serial port in RTU mode with a speed from 2400 to 38400 baud. (User manual ref: 536085).
Página 6
V1 V2 V3 VN Aux.: ieC/Ce 110... 400V AC 120... 350V DC L1 ( R ) 110... 240V AC 120... 250V DC L2 ( S ) L3 ( T ) Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 7
V1 V2 V3 VN L1 ( R ) L2 ( S ) L3 ( T ) Aux.: ieC/Ce 110... 400V AC 120... 350V DC 110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 8
S2 S1 S2 S1 S2 V1 V2 V3 VN L1 ( R ) Aux.: ieC/Ce 110... 400V AC 120... 350V DC 110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 11
DIRIS A20 PrOgramming net = 3nbl) neTwOrK (example, x 1(1BL) x 2 (2BL) x 3 (3BL) x 4 (3NBL) x 5 (4BL) x 6 (4nBL) confirm DIRIS A20 - Ref.: 538848 A...
Página 13
(example, tiMe = 20 min) x 1(20 min) x 2 (30 min) x 3 (60 min) x 4 (2 sec) x 5 (5 min) x 6 (8 min) x 7 (10 min) x 8 (15 min) confirm DIRIS A20 - Ref.: 538848 A...
Página 14
(example, tiMe = 20 min) x 1 (20 min) x 2 (30 min) x 3 (60 min) x 4 (2 sec) x 5 (5 min) x 6 (8 min) x 7 (10 min) x 8 (15 min) confirm DIRIS A20 - Ref.: 538848 A...
Página 15
DIRIS A20 PrOgramming reSeT TO zerO (example, rSet = ea) x 1 P (max P) x 2 Ea (kWh) x 3 er (kvarh) x 4 3i (max 4i) confirm DIRIS A20 - Ref.: 538848 A...
Página 16
DIRIS A20 PrOgramming BaCKligHT lCD DiSPlay (example, bACLit = U) x 1 (i) x 2 (U) x 3 (AUX) x 4 (On) confirm DIRIS A20 - Ref.: 538848 A...
Página 17
DIRIS A20 PrOgramming Serial nUmBer (example, 05312784623) SOfTware VerSiOn TO qUiT PrOgramming 3 sec. DIRIS A20 - Ref.: 538848 A...
DiRiS or manually by correcting the current connections. For the err 4, err 5 and err 6 the modification must be performed manually by correcting the voltage connections. example, teSt err 0 3 sec. 3 sec. DIRIS A20 - Ref.: 538848 A...
Página 22
DIRIS A20 COnneCTiOn TeST fUnCTiOn example, teSt err 1 3 sec. 3 sec. DIRIS A20 - Ref.: 538848 A...
> Second test operation This menu appears if the product has already been tested. This erases any changes made during the first test and retest can fully connect the product. 3 sec. Test operation DIRIS A20 - Ref.: 538848 A...
± 2% from 0.1 to 1,2 in with sinϕ = 0.5 L or C (class 1 ieC 62053-23) AUxIlIARy SUPPly IEC/CE 110 to 400 V AC 50/60 Hz ± 10 % 120 to 350 V DC ± 20 % Consumption: < 10 VA DIRIS A20 - Ref.: 538848 A...
Temperature 0 to 40°C. Maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C Transient overvoltages according to installations categories. Overvoltage categories i,ii and iii. For mains supply the minimum and normam category is ii. DIRIS A20 - Ref.: 538848 A...
LCD start-up (U or i or AUX or On condition) Serial number SOFt Software version THD i1, i2, i3 Current harmonic distortion rate THD U12, U23, U31 Phase-to-phase voltage distortion rate THD V1, V2, V3 Phase-to-neutral voltage distortion rate DIRIS A20 - Ref.: 538848 A...
Pour la sécurité du personnel et du matériel, il est impératif de bien s’imprégner du contenu de cette notice avant la mise en service. Au moment de la réception du colis contenant le DIRIS A20, il est nécessaire de vérifier les points suivants : - l’état de l’emballage, - le produit n’a pas eu de dommage pendant le transport,...
• Éviter la proximité avec des systèmes générateurs de perturbations électromagnétiques. • Éviter les vibrations comportant des accélérations supérieures à 1 g pour des fréquences inférieures à 60 Hz. Plan De DÉCOUPe mOnTage DIRIS A20 - Ref.: 538848 A...
Página 31
S2 S1 S2 S1 S2 de court-circuiter les secondaires de chaque transfor- mateur de courant. Cette manipulation peut se faire automatiquement à partir d’un produit du catalogue SOCOMeC : le PTi. Pour plus d’informations sur ce produit, merci de nous consulter. Aux.: ieC/Ce 110...
Página 32
V1 V2 V3 VN Aux.: Cei/Ce 110... 400V AC 120... 350V DC L1 ( R ) 110... 240V AC 120... 250V DC L2 ( S ) L3 ( T ) Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 33
V1 V2 V3 VN L1 ( R ) L2 ( S ) L3 ( T ) Aux.: Cei/Ce 110... 400V AC 120... 350V DC 110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 34
TC à la terre. S2 S1 S2 S1 S2 V1 V2 V3 VN L1 ( R ) Aux.: Cei/Ce 110... 400V AC 120... 350V DC 110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 37
DIRIS A20 PrOgrammaTiOn net = 3nbl) rÉSeaU (exemple, x 1(1BL) x 2 (2BL) x 3 (3BL) x 4 (3NBL) x 5 (4BL) x 6 (4nBL) confirm DIRIS A20 - Ref.: 538848 A...
Página 39
(exemple, tiMe = 20 min) x 1(20 min) x 2 (30 min) x 3 (60 min) x 4 (2 sec) x 5 (5 min) x 6 (8 min) x 7 (10 min) x 8 (15 min) confirm DIRIS A20 - Ref.: 538848 A...
Página 40
(exemple, tiMe = 20 min) x 1 (20 min) x 2 (30 min) x 3 (60 min) x 4 (2 sec) x 5 (5 min) x 6 (8 min) x 7 (10 min) x 8 (15 min) confirm DIRIS A20 - Ref.: 538848 A...
DIRIS A20 PrOgrammaTiOn remiSe À zÉrO (exemple, rSet = ea) x 1 P (max P) x 2 Ea (kWh) x 3 er (kvarh) x 4 3i (max 4i) confirm DIRIS A20 - Ref.: 538848 A...
Página 42
DIRIS A20 PrOgrammaTiOn rÉTrOÉClairage (exemple, bACLit = U) x 1 (i) x 2 (U) x 3 (AUX) x 4 (On) confirm DIRIS A20 - Ref.: 538848 A...
Pour les err 4, err5 et err 6 la modification doit se faire manuellement en corrigeant le raccordement des ten- sions. exemple, teSt err 0 3 sec. 3 sec. DIRIS A20 - Ref.: 538848 A...
Página 48
DIRIS A20 fOnCTiOn De TeST DU raCCOrDemenT exemple, teSt err 1 3 sec. 3 sec. DIRIS A20 - Ref.: 538848 A...
Página 49
ème Ce menu s’affiche si le produit a déjà été testé. Cette opération efface les modifications effectuées lors du premier test et permet de re-tester intégralement le raccordement du produit. 3 sec. Opération test DIRIS A20 - Ref.: 538848 A...
± 2% de 0,1 à 1,2 in avec sinϕ = 0,5 L ou C (classe 2 Cei 62053-23) AlIMEnTATIOn AUxIlIAIRE CEI/CE 110 à 400 V AC 50/60 Hz ± 10 % 120 à 350 V DC : ± 20 % Consommation : < 10 VA DIRIS A20 - Ref.: 538848 A...
50 % à 40 °C Surtension transitoire conformément à la catégorie d’installation. Catégories de surtension i, ii et iii. Pour la plupart des alimentations la catégorie minimum est la catégorie ii. DIRIS A20 - Ref.: 538848 A...
Para la seguridad del personal y del material, será imperativo conocer perfectamente el contenido de este manual antes de su puesta en funcionamiento. Al recibir el paquete que contiene el DIRIS A20, será necesario verificar los aspectos siguientes: - estado del embalaje, - que el producto no se haya dañado durante el transporte,...
DIRIS A20 inSTalaCiÓn reCOmenDaCiOneS • evitar la proximidad con los sistemas generadores de perturbaciones electromagnéticas. • evitar las vibraciones que provocan aceleraciones superiores a 1 g para frecuencias inferiores a 60 Hz. DimenSiOneS mOnTaje DIRIS A20 - Ref.: 538848 A...
110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC mODUlOS OPCiOneS Los DIRIS A20 pueden estar equipados con distintos módulos opcionales: • Comunicación JBUS/MODBUS (ref.: 48250082) enlace de serie RS485 JBUS/MODBUS en modo RTU con una velocidad comprendida entre 2.400 y 38.400 baudios.
Página 58
V1 V2 V3 VN Aux.: ieC/Ce 110... 400V AC 120... 350V DC L1 ( R ) 110... 240V AC 120... 250V DC L2 ( S ) L3 ( T ) Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 59
V1 V2 V3 VN L1 ( R ) L2 ( S ) L3 ( T ) Aux.: ieC/Ce 110... 400V AC 120... 350V DC 110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
Página 60
TI a tierra. S2 S1 S2 S1 S2 V1 V2 V3 VN L1 ( R ) Aux.: ieC/Ce 110... 400V AC 120... 350V DC 110... 240V AC 120... 250V DC Fus.: 0.5AgG/BS882AgG/0.5AclassCC DIRIS A20 - Ref.: 538848 A...
DIRIS A20 PrOgramaCiÓn enTrar en mODO PrOgramaCiÓn (ejemplo, COde = 100) 3 sec confirm DIRIS A20 - Ref.: 538848 A...
Página 63
DIRIS A20 PrOgramaCiÓn net = 3nbl) freCUenCia (ejemplo, x 1(1BL) x 2 (2BL) x 3 (3BL) x 4 (3NBL) x 5 (4BL) x 6 (4nBL) confirm DIRIS A20 - Ref.: 538848 A...
Página 65
(ejemplo, tiMe = 20 min) x 1(20 min) x 2 (30 min) x 3 (60 min) x 4 (2 sec) x 5 (5 min) x 6 (8 min) x 7 (10 min) x 8 (15 min) confirm DIRIS A20 - Ref.: 538848 A...
Página 66
(ejemplo, tiMe = 20 min) x 1 (20 min) x 2 (30 min) x 3 (60 min) x 4 (2 sec) x 5 (5 min) x 6 (8 min) x 7 (10 min) x 8 (15 min) confirm DIRIS A20 - Ref.: 538848 A...
Página 67
DIRIS A20 PrOgramaCiÓn VOlVer a CerO (ejemplo, rSet = ea) x 1 P (max P) x 2 Ea (kWh) x 3 er (kvarh) x 4 3i (max 4i) confirm DIRIS A20 - Ref.: 538848 A...
Página 68
DIRIS A20 PrOgramaCiÓn reTrOilUminaCiÓn (ejemplo, bACLit = U) x 1 (i) x 2 (U) x 3 (AUX) x 4 (On) confirm DIRIS A20 - Ref.: 538848 A...
Página 69
DIRIS A20 PrOgramaCiÓn númerO De Serie (ejemplo, 05312784623) VerSiÓn De SOfTware Para SalirDe la PrOgramaCiÓn 3 sec. DIRIS A20 - Ref.: 538848 A...
4, err5 y err 6, la modifi- cación puede realizarse de forma manual por medio de la corrección de la conexión de la tensión. ejemplo, teSt err 0 3 sec. 3 sec. DIRIS A20 - Ref.: 538848 A...
Página 74
DIRIS A20 COneXiÓn PrUeBa fUnCiÓn ejemplo, teSt err 1 3 sec. 3 sec. DIRIS A20 - Ref.: 538848 A...
± 2% de 0,1 a 1,2 in con sinϕ = 0,5 L o C (clase 1 ieC 62053-23) AlIMEnTACIÓn AUxIlIAR IEC/CE 110 a 400 V AC en 50/60 Hz ± 10 % 120 a 350 V DC ± 20 % Consumo < 5 VA DIRIS A20 - Ref.: 538848 A...
Página 77
Temperature 0 to 40°C. Maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C Transient overvoltages according to installations categories. Overvoltage categories i,ii and iii. For mains supply the minimum and normam category is ii. DIRIS A20 - Ref.: 538848 A...
(thd) de las intensidades THD U12, U23, U31 grado de distorsión armónico (thd) de las tensiones compuestas THD V1, V2, V3 grado de distorsión armónico (thd) de las tensiones simples DIRIS A20 - Ref.: 538848 A...