Descargar Imprimir esta página
Emerson TraxOil OW4 Instrucciones De Funcionamiento
Emerson TraxOil OW4 Instrucciones De Funcionamiento

Emerson TraxOil OW4 Instrucciones De Funcionamiento

Sistema de supervisión del nivel de aceite
Ocultar thumbs Ver también para TraxOil OW4:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 4

Enlaces rápidos

G e n e r a l i n f o r ma t i o n :
OW4/OW5 use a Hall-Sensor to measure the oil level. A magnetic float changes
its position according to the oil level. The hall sensor converts these magnetic field
changes into an equivalent signal, which is used by the internal electronic to show
with the LED's the actual oil level. If the oil level drops into the red zone OW
generates an alarm signal and the alarm contact (SPDT) changes into alarm state.
The alarm contact may be used to shut down the compressor. If the oil level comes
back to normal, the alarm will be reset. For application in refrigeration systems
according to EN 378.
Note: OW4 is developed for HFC refrigerants and subcritical CO
specially adapted to the requirements of transcritical CO
be used with dedicated types of CO
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
• According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
• In a severely contaminated system, avoid breathing acid vapors and avoid
contact with skin from contaminated refrigerant / lubricants. Failure to do
so could result in injury.
• Before opening any system make sure pressure in system is brought to and
remains at atmospheric pressure.
• Do not exceed the specified maximum ratings for pressure, temperature,
voltage and current.
• Before installation or service disconnect all voltages from system and
device.
• Note: Float contains lead and has to be recycled after operation!
S y s t e m C o m p o n e n t s : ( s e e F i g . 1 , 2 )
1. Screws (M6x45):
OW4: 3pcs, OW5: 2 pcs
2. Countersunk screw: 1 pc (OW5 only)
3. Spring washer: 3 pcs (OW4 only)
4. Sight glass OW4
5. Sight glass OW5
6. Sight glass O-ring - 33.3x2.4
7. Base unit
8. Adapter O-ring - 25.1x2.6
9. Adapter (flange or screw)
A : I n s t a l l a t i o n w i t h F l a n g e A d a p t e r s : ( s e e F i g . 1 , 2 )
Adapter types: OM0-CUA, -CCC, -CCD, -CCE, -CUD + CO
1. Remove and discard the plastic holding rings/cardboard holder from the back
side, which secure screws and sight glass during transportation.
2. Locate the grove stamped into the adapter ring in line with the main body
marking (Fig. 1).
3. Mount the base unit (7) including O-ring (8) to the adapter (9).
4. Tighten the three screws (1 & 2) only hand tight, then gradually and evenly in ½
turns until reaching the dedicated torque of 12 Nm. This procedure is mandatory
to achieve full leak tightness.
5. Remove the sight-glass from the compressor.
6. Mount O-ring (10) to the adapter (9).
for OM0-CCD/-CCE: additionally mount the teflon gasket into the compressor.
Note: In case of limited space cable plugs should be mounted prior to
installation to the compressor (see Electrical Connection).
7. Mount OW to the compressor's original sight glass connection and use original
sight glass screws - threads differ depending on compressor model.
Note: For proper function the unit must be installed horizontally (Fig. 1, 2).
8. Mounting torque: -CCD 90 Nm (wrench size 50 mm); -CCE 65 Nm (wrench
size 42 mm). All others see compressor manufacturer's installation instructions.
Note: Check Rotalock adapters for tightness after 1-2 days of operation.
B : I n s t a l l a t i o n w i t h S c r e w A d a p t e r s : ( s e e F i g . 1 , 2 )
Adapter types: OM0–CBB, -CCA, -CCB + CO
1. Screw adapter onto compressor sight glass thread (use mounting torque
specified by the compressor manufacturer) as follows:
Type -CBB: mount O-ring (10) to the adapter (9). Pay attention to proper
seating of the O-ring when mounting the adapter.
Type -CCA: apply Teflon sealant properly to adapter thread.
Type -CCB: locate O-ring (10) inside compressor sight glass thread - do not
reuse old sight glass O-ring.
Note: In case of limited space cable plugs should be mounted prior to
installation to the compressor (see Electrical Connection).
Emerson Climate Technologies GmbH
Holzhauser Str. 180 I 13509 Berlin I Germany
Oil Level Monitoring Systems
OW4 / OW5 TraxOil
systems and has to
2
compressor adapters.
2
10. Compressor O-ring:
-CBB - 28.3x1.8
-CCB - 21.9x2.6
-CUA - 33.3x2.4
-CUD - 33,3x2,4
-CCD - 26.7x1.8
-CCE - 23.5x1.8
& Teflon gasket:-CCD - 1 ¾"
-CCE - 1 ¼ "
11. Relay connector OM3-Nxx
12. Power supply cable OW-24V-3
-Versions
2
-Versions
2
www.emersonclimate.eu
Operating instruction
2. Remove and discard the plastic holding rings/cardboard holder from the back
side, which secure screws and sight glass during transportation.
3. Locate the grove stamped into the adapter ring in line with the main body
marking (Fig. 1).
4. Mount the base unit (7) including O-ring (8) to the adapter (9).
Note: For proper function the unit must be installed horizontally (Fig. 1, 2).
5. Tighten the three screws (1 & 2) only hand tight, then gradually and evenly in ½
turns until reaching the dedicated torque of 12 Nm. This procedure is mandatory
to achieve full leak tightness.
. OW5 is
2
P r e s s u r e T e s t :
After completion of installation, a pressure test must be carried out as follows:
- according to EN 378 for systems which must comply with European pressure
equipment directive 97/23/EC.
- to maximum working pressure of system for other applications.
Warning:
• Failure to do so could result in loss of refrigerant and personal injury.
• The pressure test must be conducted by skilled persons with due respect
regarding the danger related to pressure.
T i g h t n e s s T e s t :
Conduct a tightness test according to EN 378-2 with appropriate equipment and
method to identify leakages of external joints. The allowable leakage rate must be
according system manufacturer's specification.
E l e c t r i c a l C o n n e c t i o n
Connect OW-24V-3 (12) and OM3-Nxx (11) cable assemblies to OW4/5 acc. to
Fig. 2. Recommended torque for the plug screws is 0.15 Nm (hand-tight).
W i r i n g :
Note: Do not switch the compressor directly. Use compressor's power relay
instead. See Fig. 3 for connection of OW4/5 to the safety loop (SL) of a rack
controller.
• Connect the OM3-Nxx (11) cable to the relay connection according Fig. 2
BU
=
blue
BK
=
black (common)
BN
=
brown (closed in Alarm)
• Connect OW-24V-3 cable (12) wires to power supply 24VAC.
O p e r a t i o n : ( F i g . 3 )
OW4/5 are fully level controlled. The sight glass of each device is divided into
three operational zones. When the level reaches the yellow zone OW starts
switching on the yellow LED after a time delay of 10 sec. Further level drop to the
red zone will switch the alarm relay after a time delay of 20 sec (OW4) or 120 sec
(OW5).
The current status is indicated with 3 LEDs according to following table:
LED
Green
Green
Yellow Oil Level in green zone (close 40%) & OK
Yellow Oil Level in yellow zone (40 – 25%) & Warning
Red
Yellow Oil Level in red zone (25 - 0%) & Alarm
T e c h n i c a l d a t a :
Max. working pressure PS:
Test Pressure PT:
Supply voltage:
Current:
Alarm contact rating:
Alarm switch:
Time delay warning:
Times delay alarm:
Medium compatibility:
Medium temperature:
Storage, transport and ambient temperature (housing):
Protection class (IEC529EN60529):
Marking:
Date: 28.07.2015
(open in Alarm)
Status / Function
Oil Level in green zone (60 - 40%) & OK
OW4: 20 sec
OW4: HFC, CO
acc. EMC and Low Voltage Directive
OW45_OI_ML_R03_865893.docx
OW4: 60 bar
OW5: 100 bar
OW4: 66 bar
OW5: 110 bar
24 VAC, 50/60 Hz (±10%)
0.05 A
3A/230 VAC
SPDT
10 sec
OW5: 120 sec
OW5: CO
only
2
2
-20...+80 °C
-20...+50 °C
IP65

Publicidad

loading

Resumen de contenidos para Emerson TraxOil OW4

  • Página 1 O-ring. Note: In case of limited space cable plugs should be mounted prior to installation to the compressor (see Electrical Connection). Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015...
  • Página 2 O-Ring des Schauglases entsorgen - nicht wiederverwenden. I n f o r ma t i o n s g é n é r a l e s : Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015...
  • Página 3 Type -CBB: Placer le joint torique (10) sur l’adaptateur (9). Faire attention au Marquage: pour EMC & directive brasse pression, bon positionnement de l’O-ring lorsqu’on monte l’adaptateur. Type -CCA: utiliser une pâte d’étanchéité au téflon. Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015 OW45_OI_ML_R03_865893.docx...
  • Página 4 Nivel en zona Red (25 - 0%) & Alarma Roja Amarillo Nota: Compruebe siempre el apriete de los adaptadores rotalock tras 1-2 días de operación. Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015 OW45_OI_ML_R03_865893.docx...
  • Página 5 Temperatura del medio: -20…+80 °C Temp. Transporte, Almacen y Ambiente (carcasa): -20…+50 °C Protección clase (IEC529EN60529): IP65 Marcado: directivas de Compatibilidad electromagnética y bajo voltaje Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015 OW45_OI_ML_R03_865893.docx...
  • Página 6 Istruzioni operative Sistemi di monitoraggio del livello olio TraxOil OW4 / OW5 Tipo -CCA: Applicare un sigillante a base di Teflon sulla filettatura I n f o r ma z i o n i g e n e r a l i : dell’adattatore.
  • Página 7 оригинальные винты – в зависимости от модели компрессора резьбы могут отличаться. Внимание: Для обеспечения правильной работы регулятор должен быть установлен горизонтально (рис. 1, 2). Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015 OW45_OI_ML_R03_865893.docx...
  • Página 8 температура (корпус): Красный Желтый Уровень масла в красной зоне (Red) Класс защиты (IEC529EN60529): (25 - 0%) – Авария IP65 Маркировка: оборудования и по электромагнитной совместимости Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015 OW45_OI_ML_R03_865893.docx...
  • Página 9 Oil Level Monitoring Systems OW4 / OW5 TraxOil Fig. 1 Fig. 2 Fig. 3 Emerson Climate Technologies GmbH www.emersonclimate.eu Holzhauser Str. 180 I 13509 Berlin I Germany Date: 28.07.2015 OW45_OI_ML_R03_865893.docx...

Este manual también es adecuado para:

Traxoil ow5