Installation • Instalación
Installation • Instalação
2
3
4
1
wrong • no correcto
incorrect • incorrecto
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
6
5
6
correct • correcto
correct • correcto
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1. Feed pipe and fitting at least ½"!
(internal dia > 0,51 inch)
2. No filters in feed line
3. Slope in feed line > 1%!
4. Only use ball valves!
5. Pressure: min. 12 psig or 18 psig!
(check type plate for correct pres-
sure)
6. Short pressure hose!
7. For each yard of rising slope in the
outlet line, the required minimum
pressure will increase by 1.5 psig.
8
7
The rise of the outlet line must not
exceed 17 feet!
8. Collecting line min. ¾ '' with 1% slope
9. In the case of inflow problems, install
venting line.
Note: Pressure differences!
Each condensate source must be
drained separately!
Note: Venting!
If the feed line cannot be laid with
sufficient slope, it will be necessary to
install a venting line!
Note: Deflector area!
If drainage is to take place directly
from a line, it is advisable to arrange
the piping so that the air flow is diverted.
BEKOMAT 13, 13 CO, 13 CO PN25, 13 CO PN40