Safety instructions for the installation according to UL

Original − English
Approval
Underwriter Laboratories (UL), UL508 and CSA C22.2 No. 142−M1987, (UL File
Number E236341)
Ratings
Input 24 V DC, 65 W
ƒ
For use on an isolated power supply rated 24V DC 4A max.
ƒ
Max. ambient temperature 40°C
ƒ
Max. surrounding temperature 50 °C
ƒ
Optional communication ratings:
ƒ
RS232−Connection (APL and DPL version only): max. 3 A
USB−Connection (DVI version only): max. 1 A
PS/2−Connection: max. 1 A
VGA−Connection (APL version only): max. 4 A
FBAS−Connection (APL version only): max. 4 A
DVI−Connector (DVI version only): max. 4 A
DPL−Connection (DVI version only): max. 4 A
External Power Supply for DVI/USB Extender: max. 4 A
Video−DSUB Connection for DVI/USB Extender: max. 4 A
Data−DSUB Connection for DVI/USB Extender: max. 4 A
Environmental ratings: If these devices are mounted into a door or front
ƒ
cover of an enclosure: Type 1 Enclosure.
O
Warnings!
Conditions of acceptability
ƒ
ƒ
Field Wiring Markings
Wiring Terminal MSTB 2,5/3−STF−5,08:
ƒ
ƒ
ƒ
MA_ELx0xx DE/EN/FR/ES/IT 2.0
Safety instructions for the installation according to UL
These devices are for Type 1 front panel mounting only.
The external power supply connection is suitable for field wiring.
An isolated power supply rated 24 V DC, 4 A max. must be used.
Use Copper Wire only.
AWG 18 ... AWG 12 (0.82 mm
Torque 5...7 lb−in (0.5 ... 0.6 Nm)
l
Safety instructions
2
2
... 3.3 mm
)
2