28 mm.
HUMIDITY CONTROLLER - WH8040
1. INSTALLATION OPENING SIZE: 70 X 28 mm.
2 WIRING DIAGRAM:
12
load
Terminals 1 and 2: Normally opened contact of relay
Terminals 3 and 4: Connect the power
Terminals 5 and 6 and 7: Connect the Humidity sensor
Terminals 8 and 9: Connect Temperature sensor
3. ELECTRICAL PERFORMANCE:
Humidity measurement range: 1% ~99% Humidity control range: 1% ~99% Humidity
measurement error: 3% Sensor Type: HM40
Symbol
Details
Control accuracy: 1 %
Working voltage: for detailed information of the input voltage, please see the notes on the
Humidification
products
HC
/Dehumidification
Working current: <2W
Hysteresis
D
Relay contact point current: AC 5A/220V Data storage: Yes
The
Working temperature: 0 ºC ~ 50 ºC
minimum set
LS
Storage temperature: -10 ºC ~ 60 ºC
limit
The
maximum set
HS
4. KEY INSTRUCTIONS:
limit
Humidity
CA
RST:
calibration
Press RST key to switch on and off, press the RST key on the power-off state once to turn on, on
Delay time
PT
the power-on state, press the RST key for three seconds and hold on, then it will be off.
SET:
A: Press the SET key once to enter the temperature control setting, press
"▲" or "▼" button to adjust, press "▲" or "▼" button for three seconds and hold to enter the
fast adjusting mode, press the SET key again to exit setting mode.
B: Press and hold SET key for three seconds to enter the system menu settings, press the "▲"
or "▼" key to select the adjustment menu, press SET key once to enter the appropriate para-
meter settings, press "▲" or "▼" to adjust the parameters needed to be modified, after being
adjusted, press the RST key to exit, or exit as the system delay for 5 seconds.
▲ : Up key
▼ : Down key
5. OPERATING INSTRUCTIONS:
LED Status Description:
The WORK lights at the left side of the screen are used as working indicator lights, flashing indi-
cates the delay of cooling or heating, if the LED is always on, it indicates it is on the status of Hu-
midification or Dehumidification.
The SET light at the left side of the screen lights is used as setting indicator lights, if the LED is
always on, it indicates it is on the status of setting.
Function Instructions:
Press RST key to open the Humidity Controller, on the running status, press this key for 3 se-
conds, then the Humidity Controller can be turned off.
Power
V
3
4
5
6
power input
Setting
Factory
settings
range
H/C
C
1~15
5
-50
-50~110
110
-50~110
0
-5~+5
1
0~10
+
NTC
7
8
9
Units
ºC
ºC
ºC
ºC
Minutes
13