Installation
Installation
NOTICE! Avoid cleaners containing organic
solvents, alcohols, and hydrocarbons.
Rinse with water after cleaning.
Supplies Required:
• (3) ³⁄₈" wall fasteners and bolts
• Pipe sealant
• Piping to ½" IPS water supply inlet on unit
• Piping to 1¼" IPS drain outlet
• Sign-mounting hardware
Step 1: Install inlet drain fitting
The top of the eyewash heads should be
33"–45" (838mm–1143mm) from the floor.
1 . Position the inlet drain fitting over the 1¼" drain
outlet pipe from wall .
2 . Using the inlet drain fitting as a template, mark
the bolt hole locations on the wall OR install three
suitable fasteners (supplied by installer) for ³⁄₈"
bolts in the wall at the marked hole locations (see
Figure 1) .
3 . Bolt the inlet drain fitting to the wall or wall
fasteners using ³⁄₈" bolts (supplied by installer) .
Step 2: Assemble eye/face wash
1 . Assemble eyewash components as shown in Figure 2 .
• Apply pipe sealant (supplied by installer) to all male-threaded pipe joints .
• Use the rubber grip pad provided or a strap wrench around pipes when tightening to prevent marring the
Bradtect
protective, safety yellow coating . Place the grip pad on the pipe, then put the wrench over the
®
grip pad and turn the pipe with the wrench .
Step 3: Connect water supply
1 . Connect the water supply piping (supplied by installer) to the ½" IPS inlet on the eye/face wash .
2 . Connect the tailpiece to the 1¼" IPS drain outlet on the eyewash .
3 . Mount the safety sign to the wall using sign-mounting hardware (supplied by installer) .
4 . Open the water supply lines . Test for leaks and adequate water flow .
Bradley • 215-158FW Rev L; ECN 14-05-001
Figure 1
Wall
13¼"
(337mm)
Ø 10" (254mm)
15½" (394mm)
8¹⁄₈"
(206mm)
2¼"
(57mm)
Ø ³⁄₈"
7½"
(9mm)
5¼"
(191mm)
(133mm)
1/13/2014
S19-220FW
4½"
(114mm)
8¼"
(210mm)
4"
(102mm)
36" (914mm)
Suggested
Height to
Floor
29½"
(749mm)
Suggested
Height to
Floor
3