INSTALLATION AND MAINTENANCE INSTRUCTIONS
CR-6
Six Relay Control Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Maximum IDC Wiring Resistance:
Accessories:
Wire Gauge:
Relay Current:
CURRENT RATING
3A
2A
1A
.5A
BEFORE INSTALLING
This information is included as a quick reference installation guide. If the
modules will be installed in an existing operational system, inform the op-
erator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The CR-6 Six Relay Control Module is intended for use
in an intelligent alarm system. Each module is intended for Form-C switching
applications, which do not require wiring supervision for the load circuit. A
single isolated set of dry relay contacts is provided for each module, which is
capable of being wired for either normally open or
normally closed for each operation. Each module has its own address. A pair
of rotary code switches is used to set the address of the first module from 01 to
94. The remaining modules are automatically assigned to the next five higher
addresses. Provisions are included for disabling a maximum of three unused
modules to release the addresses to be used elsewhere. Each CR-6 module also
has panel controlled green LED indicators. The panel can cause the LEDs to
blink, latch on, or latch off.
D500-65-00
15-32 VDC
1.45 mA
32 mA (assumes all six relays have been switched once and all six LEDs solid on)
-10°C to 55°C
10 to 93% Non condensing
17.3cm H x 14.7cm W x 3.2cm D
40 ohms
Suitably grounded metallic cabinet
0.9mm2 - 3.25mm2
30 mA/Relay Pulse (15.6 mS pulse duration) pulse under panel control
MAXIMUM VOLTAGE
30VDC
30VDC
30VDC
30VDC
LOAD DESCRIPTION
Resistive
Resistive
Inductive (L/R=2ms)
Inductive (L/R = 5ms)
CONTENTS INCLUDE:
(6) 1 x 3 Terminal Blocks
(1) 1 x 4 Terminal Blocks
(2) Nuts
(4) Screws
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
control panel only.
The CR-6 Module shall be mounted in a suitably grounded Metallic Cabinet
for EMC compliance.
1
Pittway Technologica S.p.A
Via Caboto 19/3
34147 Trieste, Italy
APPLICATION
Non Coded
Coded
Coded
Coded
(2) 3.2 cm Stand offs
(1) Shunt
(NOTE: For the disable position,
not more than one shunt shall be
installed at the same time)
I56-2255-004

Publicidad

loading

Resumen de contenidos para System Sensor CR-6

  • Página 1 EMC compliance. addresses. Provisions are included for disabling a maximum of three unused modules to release the addresses to be used elsewhere. Each CR-6 module also has panel controlled green LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
  • Página 2: Relay Connections

    29, 30, 31, 32, and 33. DO NOT set the lowest address above 94, as the other modules will be assigned to nonexistent addresses. FIGURE 1: WIRING AND PROGRAMMING ThE CR-6 MODULE RELAY CONNECTIONS BASE ADDRESS...
  • Página 3 DESCRIzIONE GENERALE più di una derivazione alla vota) Il modulo di controllo a sei relè CR-6 è stato progettato per l’uso in sistemi d’allarme intelligenti. Ogni modulo è destinato ad applicazioni di switching REQUISITI DI COMPATIBILITÀ con modulo C che non richiedono la supervisione del cablaggio del circuito Per garantire un corretto funzionamento, collegare questo modulo solo ad un di carico.
  • Página 4 Se ad esempio la derivazione per la disabilitazione dell’indirizzo si trova L’intero cablaggio del CR-6 passa attraverso delle morsettiere Per es- su “due” e l’indirizzo dello switch di riferimento è impostato su 28, ai eguire le connessioni elettriche, rimuovere circa 5 mm di materiale iso- moduli verranno assegnati gli indirizzi 28, 29, 30 e 31.
  • Página 5: Módulo De Control Con Seis Circuitos De Salida En Forma Relé

    DESCRIPCIÓN GENERAL El Módulo de Control CR-6 ha sido diseñado para su uso en un sistema de al mismo tiempo) alarma inteligente. Cada módulo se utiliza en aplicaciones con relés en Forma C, que no necesitan supervisión por cable desde el circuito de carga.
  • Página 6: Conexiones Del Relé

    29, 30, 31, 32 y 33. NO debe configurar la dirección más baja por encima del número 94, ya que al resto de los módulos se les adjudicarían direcciones que no existen. FIGURA 1. CABLEADO Y PROGRAMACIÓN DEL MÓDULO CR-6 CONEXIONES DEL RELÉ DIRECCIÓN BASE...
  • Página 7 Es besteht die Möglichkeit bis max. drei nicht benötigte Module abzuschalten und deren Adressbereich für andere Anwendungen frei zu geben. Jedes CR-6 Modul hat eine, von der Zentrale gesteuerte, grüne LED-Anzeige. Die Zentrale kann die LED blinkend, folgend ein oder folgend aus ansteuern.
  • Página 8 5 Modul die Adressen 29 - 37. Stellen Sie niemals eine Ersta- dresse über 94 ein, weil dann die nächsten Module als nicht vorhanden interpretiert werden. ABBILDUNG 1: VERDRAhTUNG UND PROGRAMMIERUNG DES CR-6 MODULES RELAIS ANSCHLUSS MODUL ADRESSE VON DER ZENTRALE ODER N.C.