BATTERY INSTALLATION

PRECAUTION!
Make sure that the inverter AC and DC connections are turned off before connecting the power cable to the battery bank.
Make sure that the power switch of the inverter and the battery are turned off before connecting the power cable to the battery.
NOTE
USE PROPER BRACKETS, SUPPORTS AND/OR STRAPS TO HANDLE THE WEIGHT OF THE BATTERY. A WELL
VENTILATED, HEAVY DUTY BATTERY CABINET IS RECOMMENDED
DC WIRING
It is suggested that the batteries are kept as close as possible to the inverter or DC load. The following is a suggested wiring option for 1meter
DC cable. Please find the following minimum wire size, in case of having DC cables longer than 1m, please increase the cross section of the
cable to reduce the losses.
Performance of any product can be improved by thicker and shorter cables, so if in doubt, round up and keep the length as short as possible.
WARNING!
The torque rating range for the DC terminals is 9NM-12NM, and the suggested torque is
9NM. Over torqueing may cause the bolt to break

PERFORMANCE

PERFORMANCE CONDITIONS
Installation Location
Operating Temperature
Recommended operating temperature
Humidity
Altitude
Cooling Strategy
POWERING ON THE BATTERY
Put the battery in operation by taking the following steps:
1. Turn on the power switch after installing the battery.
2. The internal main relay will pick up and all the LEDs will turn on.
3. If the battery is successfully initialized, then the RUN LED indicator on the front should turn on in green. SOC LEDs indicators will show the
current capacity of the battery.
4. Turn the inverter on.
WARNING!
If the battery stays off, it indicates FAULT or fails to operate, do not use
this battery.
www.intipv.com
No.
Model
DC output voltage
ILFP-1536
25,6Vdc
1
ILFP-2560
25,6Vdc
2
ILFP-3072
25,6Vdc
3
ILFP-3840
25,6Vdc
4
ILFP-512024
25,6Vdc
5
6
ILFP-5120
51,2Vdc
Indoor (Wall-Mounted or Flat-Mounted)
-25 to 55°C
15 to 30°C
5% to 95%
Max. 2.600m
Natural Convection
Wire gage
AWG #2
AWG #2
AWG #2
AWG #2
AWG #2
AWG #3