Technical Parameters; Communication Protocol - Elko EP iNels DMD3-1 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 11

Technical parameters

Inputs
Angle of motion detection:
Recommended installation
height:
Changing the PIR sensitivity:
PIR scan type:
Default setup PIR:
Temperature measuring:
Scope and accuracy of
temp. measurement:
Humidity measurement:
Humidity meas. range:
Humidity meas. acc
urancy:
Light Metering:
Detection angle:
Measuring range:
Number of control buttons:
Outputs
Indication red LED:
Indicating blue LED:
Indication green LED RUN:
Communication
Interface:
Power supply
From iNELS BUS:
Rated current:
From DALI BUS:
Rated current:
Dissipated power:
Connection
Terminals:
Operating conditions
Operating temperature:
Storing temperature:
Protection degree:
Operation position:
Installation:
Dimension and weight
Dimension:
- installation hole diameter:
- diameter visible:
Weight:
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualifi cation, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting,
servicing, executing any changes, and repairing it is essential to observe safety regulations, norms,
directives and special regulations for working with electrical equipment. Before you start working
with the device, it is essential to have all wires, connected parts, and terminals de-energized. This
instruction manual contains only general directions which need to be applied in a particular
installation. In the course of inspections and maintenance, always check (while de-energized) if
terminals are tightened.
TECHNICAL SUPPORT | E-mail: support@inels.com | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Made in Czech Republic
DMD3-1
140 °, 4 m
2.5 - 3 m
YES, 0.. 127 (max. sensitivity)
single / dual
99 dual
YES, built-in temperature sensor
-25.. +110 °C; ± 0.3 °C
YES
0 .. 99% RH
± 4 % RH
YES
± 55 °
1 - 100 000 lx
1
identifi cation DALI MASTER /
communication options
PIR Activation
communications / unit status
Installation BUS iNELS DALI
27 V DC, -20 / +10 %
18 mA
16 V (max. 23 V)
27 mA
max. 0.5 W
2
0.3 - 0.8 mm
-20 .. +55 °C
-30 .. +70 °C
IP20
vertical
celling
Ø 76 x 73 mm
60 mm
76 mm
81 g
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: elko@elkoep.com

Communication protocol

24 bit DALI MASTER frame
Bit 23
Bit 22 – 17
Bit 16
0
64 short addresses
0
Instance number:
1
2
3
4
Light intenzity [Lux] = 10exp(Light intenzity step/174)
Humidity[%] = Humidity step/10
Temperature[°C] = (16*Temperature step – 4000)/100
Supported DALI commands (IEC 62386-103:2014)
TERMINATE
INITIALIZE
RANDOMIZE
COMPARE
WITHDRAW
SEARCHADRH
SEARCHADRM
SEARCHADRL
PROGRAM_SHORT_ADDRESS
VERIFY_SHORT_ADDRESS
QUERY_SHORT_ADDRESS
DTR0
DIRECT_WRITE_MEMORY
IDENTIFY_DEVICE
SET_SHORT_ADR
ENABLE_WRITE_MEMORY
QUERY_DEVICE_STATUS
QUERY_VERSION_NUMBER
Bit 15
Bit 14 -10
1
32 instance numbers
event data
Event data DMD-3
Motion – bit 0
Light intenzity step (1 sec)
Humidity step (10 sec)
Temperature step (10 sec)
Bit 9 – 0
2/2