3.3 Especificaciones eléctricas generales para FN 3442/FN 3443 (filtros de 60 Hz)
Nominal operating voltage:
Voltage tolerance range:
Operating frequency:
Network:
Nominal motor drive input power rating:
Total harmonic current distortion THID:
Total demand distortion TDD:
Efficiency:
3)
Drive dc-link voltage:
High potential test voltage:
5)
SCCR:
Protection category:
Pollution degree:
Cooling:
Overload capability:
Capacitive current @ no load:
Ambient temperature range:
Flammability class:
Insulation class of magnetic components:
Design corresponding to:
MTBF @ 45°C/415 V (Mil-HB-217F):
MTTR:
Lifetime (calculated):
Safety monitor output signal:
1)
THID ~5% at rated power for filter <4kW.
2)
System requirements: THVD <2%, line voltage unbalance <1%
Performance specification for six-pulse diode rectifiers. SCR rectifier front-ends produce different results, depending upon
the firing angle of the thyristors.
3)
Conditions: line impedance <3%
4)
Repetitive tests to be performed at max. 80% of above levels, for 2 seconds.
5)
External UL-rated fuses required.
6)
Please check the inlet air flow required for cooling in Tabla 17
7)
I
= I
×((70°C-T
derated
nominal
2)
2)
4)
)/25°C)
amb
3x 380 to 415 V CA
3x 342 to 456 V CA
60 Hz ±1 Hz
TN, TT, IT
1 to 240 HP (0.9 to 177 kW)
1)
<5% @ rated power
According to IEEE 519
>98% @ nominal line voltage and power
-5% ~ +10% nominal V
P → E 2160 VAC (1s)
100kA, fuses according UL class J
IP 00, IP 20
PD3 (according to standard IEC 60664-1)
Internal fan cooling or external cooling
1.6x rated current for 1 minute, once per hour
<20% of rated input current, at 480 V AC
-25°C to +45°C fully operational
+45°C to +70°C derated operation
-25°C to +85°C transportation and storage
UL 94V-2
N (200°C), H (180°C)
Filter : UL 61800-5-1, EN 61800-5-1
Chokes : EN 61558-2-20 or EN 60076-6
>200,000 hours
<15 minutes (capacitor modules and fan modules)
≥10 years
Thermal switch NC 180° C (UL-approved) to detect
overload of chokes