Installation
Flush the water supply lines before beginning installation and after installation is complete. Test the unit for
leaks and adequate water flow. Main water supply to the eyewash should be "ON" at all times. Provisions
shall be made to prevent unauthorized shutoff.
Emergency equipment must be supplied with tepid water (60°F to 100°F/15.6°C to 37.8°C). Any prolonged
exposure to near freezing water affects the body's ability to maintain body temperature, increasing the risk of
hypothermia.
Before installing this product, ensure that there are adequate clearances around the product and activation of
the product does not interfere with other products or obstructions.
Avoid cleaners containing organic solvents, alcohols and hydrocarbons. Rinse with water after cleaning.
The installation and location of all safety drench showers, eye and eye/face washes must comply with the
requirements of ANSI/ISEA Z358.1.
Read this installation manual completely to ensure proper installation, then file it with the owner or
maintenance department. Compliance and conformity to drain requirements and other local codes and
ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before discarding any packaging
material. If any parts are missing, do not begin installation until you obtain the missing parts.
The ANSI/ISEA Z358.1 standard requires an uninterrupted supply of flushing fluid. Bradley plumbed
emergency fixtures require a minimum of 30 PSI (0.21MPa) flowing pressure.
Self-closing spring-loaded valves are not UL classified to ANSI/ISEA Z358.1.
Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing
fluid supply is present and any sediment build-up in the supply line is cleared. Emergency equipment should
be inspected monthly to address any maintenance issues ensuring the equipment is in good operating
condition and that there are no signs of wear.
Workers who may come in contact with potentially hazardous materials should be trained regarding the
placement and proper operation of emergency equipment per ANSI/ISEA Z358.1.
For questions regarding the operation or installation of this product, visit www.bradleycorp.com or call
800-BRADLEY (272.3539).
Product warranties and parts information may also be found under "Products" on our web site at
bradleycorp.com.

Supplies Required:

Piping to ½" NPT water supply inlet on unit
Pipe sealant
Sign-mounting hardware
Bradley • 215-1408 Rev. S; ECN 15-05-042
S19-270HD, -270HW, -270JD, -270JW, 274HD, 274HDR, 274HW, 274JD, 274JW
WARNING

IMPORTANT

CAUTION
NOTICE
Local codes may require the installation of a backflow
prevention valve to complete proper installation.
Compliance with local codes is the responsibility of the
installer. Valve must be tested annually to verify that it
is functioning properly. Backflow prevention valves are
not included with the fixture and may be supplied by
the contractor or purchased from Bradley Corporation.