Installation - Bradley S19-270HD Manual De Instalación

Ocultar thumbs Ver también para S19-270HD:
Tabla de contenido

Publicidad

S19-270HD, -270HW, -270JD, -270JW, 274HD, 274HDR, 274HW, 274JD, 274JW

Installation

Halo eye/face wash unit is shown on a sample 25" (635mm) deck. Other units are similar.
Minimum dimensions necessary to contain splashing from Halo units are shown.
Apply pipe sealant (supplied by installer) to all male-threaded pipe joints. The top of the eyewash heads should be positioned
a minimum of 33" (838mm) and a maximum of 45" (1143mm) from the floor and 6" (152mm) from the nearest obstruction.
Proper faucet shank/handle
clearance and recommended
minimum splash containment
dimensions must be considered
when selecting the desired
location for mounting.
25"
(635mm)
Connect the water supply using
C
piping (supplied by installer) with
½" NPT female threaded end .
6
A
"ON" Position
E
10/5/2017
Ø ⁷⁄₈"
1¼"
(32mm)
Ø ³⁄₁₆"
¼"
(6mm)
Deck Mounting Pattern .
Drill (3) holes as shown .
3¾"
2½"
(95mm)
(64mm)
Ref .
Min .
Slowly open the water
supply lines to relieve air
and pressurize the valve .
Test the unit for leaks
and adequate flow .
Bradley • 215-1408 Rev. S; ECN 15-05-042
B
Deck
"OFF" Position
11¹⁄₈"
(283mm)
Ref .
15¼"
(387mm)
Ref .
2¹⁄₈"
(54mm)
Min .
D
To
Wall
Installation

Publicidad

Tabla de contenido
loading

Tabla de contenido