Conventional resettable manual callpoint
991j/01
IC0020 series manual call points are certified and approved according to EN54-11 -
Manual call points.
IC0020 manual call points are specially designed to operate with
conventional control panels.
The device trigger element and red status LED are located in the
front case of the device. The LED will light up when the device is
activated.
The device details and information regarding the connection
terminals can be found on the label inside the device housing.
The device provides connectors for the resistance jumper. The
position of the jumper defines the alarm resistance, as follows:
Position
RL
RH
The device package contains two fork-end keys which can be used
to open the housing and reset the device
The flush-mount backbox and the protective front plate are
accessory items and must be purchased separately.
A
B
C
D
Backbox with fixing screw holes and cable entry
E
F
Fixed back-locking clip positions
G
H
I
J
K
Connectors for the resistance jumper
TECHNICAL SPECIFICATIONS
Operating voltage
Resistance between terminals
"+" and "-" in the event of alarm
Operating temperature
Humidity
(without condensation)
Dimensions (HxWxD)
Weight
IC0020
Alarm resistance
260 Ohm
660 Ohm
Callpoint button - rear
Details label
Terminals
Fixed back-locking clips
Back-locking backbox clips
Back-locking clip positions
Reset key slot
Protection front plate clips
10-30 Vdc
260 - 660 Ohm
-10°C / +55°C
95% RH
84 x 84 x 45 mm
Description
J
A
126 g
0832
0832-CPR-F0442