The IC0020 manual callpoint uses a simple mechanism which
consists of a rigid plastic operating element and an over-center
spring mechanism. Pressing on the black spot simulates "Break
Glass" activation and triggers an alarm.
Activation is signalled by a yellow and black striped flag which
drops into view on the upper part of the frontplate and by solid
light on the red LED.
The IC0020 manual call point is reset by inserting the key
provided into the key slot and by pushing the trigger
mechanism upwards as far as possible, after which the key
must be turned clockwise until the mechanism locks back into
position.
The reset procedure must be carried out in accordance with the
above instructions, otherwise, you may damage the manual call
point and/or its key.
Successful rest causes the flag to withdraw and the red LED to
go off.
Connect the IC0020 manual call point to the control panel using
2 wires.
The backbox has standard wall-mount anchor screw holes.
Insert the forked-end of the reset key into the two slots and
push against the back-locking clips to open the manual call
point.
Once all the devices are installed, refer to the control panel
manual for the instructions relating to the configuration and
end-of-line resistance.
Test and maintenance
Test the manual call point immediately after installation and
then regularly during the periodic tests which must be carried
out in accordance with the local laws in force.

Warnings and limitations

IC0020 manual call point is not suitable for outdoor installation
unless adequately housed inside a heavy duty weather proof
box.
CE marking and certifications
DoP, EC DoC and certificates related to this product can be
downloaded from the following link:
www.inim.biz/certifications
INIM Electronics reserves the right to change
the technical specifications of this product
without prior notice.
INIM ELECTRONICS S.R.L.
Via Dei Lavoratori 10 - Fraz. Centobuchi
63076 Monteprandone (AP) - Italy
Tel. +39 0735 70 50 07
Fax + 39 0735 70 49 12
www.inim.biz info@inim.biz
4
Activation
Reset
Installation
ATTENTION!
Conventional Type A indoor re-settable manual call point for
fire detection and fire alarm systems installed in buildings