Descargar Imprimir esta página
Intesis INWMPFGL001R000 Manual De Instrucciones

Intesis INWMPFGL001R000 Manual De Instrucciones

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Interface INWMPFGL001R000
Safety instructions
WARNING
Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may
damage seriously the interface and/or the AC indoor unit.
• This interface must be installed by accredited technical personnel (electrician, installer or authorized technical personnel) and
following all the safety instructions.
• This interface must only be installed in a restricted access location.
• Before manipulate the AC indoor unit be sure it is completely disconnected from Mains power.
• In case of installation of the interface inside the AC indoor unit, fix the interface and communication cables preferably to any
appropriate point of the plastic cover of the unit taking care of no blocking free movement of mobile parts and as far as possible
from tubes containing liquids and power cables.
Installation instructions
1. Unplug the Fujitsu system from mains electricity.
2. Connect Intesis RC port to Fujitsu Indoor Unit RWB terminals. Respect the polarity according to the following scheme.
3. Connect Wired Remote Control in parallel to RWB bus (if present).
4. Configure the Intesis switches (see below).
5. Plug the Fujitsu system to mains electricity.
1. Wi-Fi Access Point or Router
2. Intesis device
3. Wired Remote Controller
4. Indoor unit
1
Switch configuration
Binary value
Decimal
Switches
value
b
...b
1 2 3 4
0
4
0xxx
0
 x x x
1xxx
1
 x x x
x0xx
0
x  x x
x  x x
x1xx
1
xx0x
0
x x  x
xx1x
1
x x  x
xxx0
0
x x x 
xxx1
1
x x x 
SW3: This switch determines the performance of the device. Running in High Performance Mode means maximum consumption and maximum device performance.
SW4: This switch determines the Wi-Fi range of the device. Maximum range is set by default. Consider that changing this switch may affect to device WiFi communication,
happening a device in a running installation not to reach the current access point or Wi-Fi network to which is connected.
NOTE: Remember that you need to power cycle the climate system or the Intesis device for the changes in the switches to be applied.
Rev.1.0
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
4
Description
Slave - A Fujitsu Controller must be present in RWB bus configured as Master (Default value)
Master – Fujitsu Controller not needed in RWB bus. If it exists, it must be configured as Slave
Machine type: RAC inverter model G series, VRF J-II, VRF V-II or VRF VR-II 10 (Default value)
Machine type: RAC inverter, RAC non-inverter, VRF V, VRF S or VRF J
Low Power Mode
High Performance Mode (Default value)
Wi-Fi power is limited
Max Wi-Fi power (default value)
More information about the product and its manuals can be found at:
https://intesis.com/products/ac-interfaces/fujitsu-gateways/fujitsu-ascii-wifi-vrf-fj-rc-wmp-1
2
BWR BUS
Installation Manual
BWR
connector
OPTIONAL
3
URL
https://www.intesis.com
1 / 2

Publicidad

loading

Resumen de contenidos para Intesis INWMPFGL001R000

  • Página 1 Wi-Fi network to which is connected. NOTE: Remember that you need to power cycle the climate system or the Intesis device for the changes in the switches to be applied.
  • Página 2 Wi-Fi del dispositivo, ocasionando que un dispositivo en funcionamiento no alcance el punto de acceso o red Wi-Fi a la que se encuentra conectado. NOTA: Recuerda que debes reiniciar el Sistema de Clima o el dispositivo Intesis para que los cambios en los interruptores se apliquen.