POWER WIRING
Refer to the input voltage rating marked on the fixture, and then wire according to
the diagram and table below.
POWER
GROUND
Low voltage fixture (120–277 V ± 15%)
Supply voltage
120 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
208 VAC, 3 Ф derived from 3 Ф,
208/120 V panel
240 VAC, 1 Ф derived from 1 Ф,
240/120 V panel
240 VAC, 1 Ф derived from 3 Ф,
240/120 V panel, B phase wild
277 VAC, 1 Ф derived from 3 Ф,
480/277 V panel
10
L1
L1 (BLACK IN US/CA/MX; BROWN
OUTSIDE US/CA/MX)
L2
L2 (WHITE IN US/CA/MX; BLUE
OUTSIDE US/CA/MX)
GROUND (GREEN IN US/CA/MX; GREEN
W/YELLOW OUTSIDE US/CA/MX)
Fixture's L1 (black)
connects to
H (black)
L1 (black), L2 (red), or L3
(blue)
L1 (black)
L1 (black), L2 (orange), or
L3 (blue)
L1 (brown), L2 (orange), or
L3 (yellow)
FIXTURE
Fixture's L2 (white)
connects to
N (white)
L2 (red), L3 (blue), or L1
(black)
L2 (red)
L2 (orange), L3 (blue), or
L1 (black)
N (white)
WWW.BIGASSFANS.COM
© 2019 DELTA T LLC