Auxiliary
and
Relays Test
Lock
Tamper and
Override Test
RS-232 Test
Leave One-
Touch™ Active
Test mode
17642v3.0
Open the door contact.
Present a key to a
reader, press the
Request to Exit switch
and open the door
contact simultaneously.
Remove link to 0V on
tamper or open circuit
tamper switch.
Remove link to 0V on
emergency override or
leave open circuit
tamper switch.
Remove the link
between TAMP and 0V
on the Tamper &
Override terminal block.
Remove the link
between OVRD and 0V
on the Tamper &
Override terminal block.
Link Tx and Rx on the
RS-232 terminal block.
Hold down the One-
Touch™ button for less
than 2 seconds.
One-Touch™ Test
mode will automatically
be timed out after 1 hour
and on power down and
up.
The door green LED
flashes four times and the
red LED is lit.
The appropriate auxiliary relay is activated.
Both auxiliary relay is activated.
The auxiliary relay is activated.
The auxiliary relay is activated but the door relays
are uneffected.
Both auxiliary and lock relays are activated, the
door opens and the lock operates.
The red and green RS-
232 LEDs are lit.
The green system
status LED returns to its
normal flash rate.
The reader LED
flashes four times.
There is no effect at the
reader.
The reader LED returns
to its normal operation.