DKG-307 User Manual
V-01.01
(22.04.2005)
The parameters from P_155 to P_158 define the exerciser operation.
Pgm Definition Unit Std Val Description
155 Exercise start day and
hour
(-) <168 This parameter defines the start day and hour
of the exerciser.
Values higher or equal to 168 mean that the
exerciser is off.
The exercise may be selected to start at the
beginning of the any hour of the week. The
parameter value is the hour count of the start
time.
Examples:
0 = exercise starts at Monday 00:00
1 = exercise starts at Monday 01:00
8 = exercise starts at Monday 08:00
24 = exercise starts at Tuesday 00:00
167 = exercise starts at Sunday 23:00
168 = exerciser off
If a daily exercise is selected with parameter
P_158=0, then the day information is don't
care and the exercise will be performed every
day regardless of the day selection.
If the monthly exercise is selected with
parameter P_158=2 then the exercise will be
performed during the first 7 days of each month
at the programmed day and hour.
156 Exercise duration min. 10 This parameter defines the exercise duration
and programmed in 10 minute steps up to 24
hours.
157 Exercise off_load/on_load - 0 If this parameter is set to 0 the genset will not
feed the load during exercise. If it is set to 1,
then the load will be transferred to the genset
during the exercise.
158 Daily / Weekly / Monthly Exercise
- 1 0: exercise every day (the exercise will be
performed every day regardless of the day
selection with parameter P_155).
1: exercise once per week
2: exercise once per month (the exercise will
be performed during the first 7 days of each
month at the programmed day and hour).
The parameters from P_159 to P_164 adjust the date and time.
Pgm Definition Unit Std Val Description
159 Year - 00-99 Last two digits of the current year.
160 Month - 01-12 Current month.
161 Date - 01-31 Current day of the month.
162 Day - 0-6 Current day of the week.(0=Monday,
1=Tuesday, 2=Wednesday, 3=Thursday
4=Friday, 5=Saturday, 6=Sunday)
163 Hour - 00-23 Current hour of the day.
164 Minute - 00-59 Current minute of the hour.
Manual DKG-307 ESPAÑOL
-
27 -