INSTALLATION AND MAINTENANCE INSTRUCTIONS
IM-10
Ten Input Monitor Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum SLC Wiring Resistance:
Maximum IDC Wiring Resistance:
Maximum IDC Voltage:
Maximum IDC Current:
BEFORE INSTALLING
This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed
in an existing operational system, inform the operator and local
authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the
modules. This system contains static sensitive components.
Always ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the body. The
housing cabinet should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user
of this equipment.
GENERAL DESCRIPTION
The IM-10 Ten Input Monitor Module is intended for use in an
intelligent alarm system. Each monitor module is intended to
interface between a control panel and normally open contact
devices, such as pull stations. A common SLC input is used for
all modules, and the initiating device loops share a common
supervisory supply and ground. Otherwise, each monitor oper-
ates independently from the others. Each module has its own
unique address.
A pair of rotary code switches is used to set the address of the
first module from 01 to 90. The remaining modules are automati-
cally assigned to the next nine higher addresses. Provisions are
included for disabling a maximum of two unused modules to
release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(6) 1 x 4 Terminal Blocks
(2) Screws
(3) Shunts
Shipped on Board:
(1) Shunt
D500-66-00
15-32 VDC
3.5 mA
60 mA (assumes all ten LEDs solid on)
–10°C to 55°C
10 to 93% Non condensing
17.3cm H x 14.7cm W x 3.2cm D
Suitably grounded metallic cabinet
0.9mm 2 - 3.25mm 2
40 Ohms
40 Ohms
12 VDC
1 mA
(2) 3.2 cm Stand offs
(10) 47k Ohm
End of Line Resistors
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
listed compatible system control panel.
The IM-10 Module shall be mounted in a suitably grounded
Metallic Cabinet for EMC compliance.
WIRING
NOTE:
All wiring must conform to applicable local codes,
ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. All wiring to the IM-10 is done via terminal blocks. In order
to properly make electrical connections strip approximately
.6 cm of insulation from the end of wire, sliding the bare end
of the wire under the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module
(between 01 and 90).
The remaining modules are automatically assigned to the next
nine higher addresses. For example, if the base address switch is
set to 28, the next nine modules will be addressed to 29, 30, 31,
32, 33, 34, 35, 36, and 37.
DO NOT set the lowest address above 90, as the other modules
will be assigned to nonexistent addresses.
4. A shunt is provided to disable a maximum of two unused
modules. Modules are disabled from the highest address and
work downward. If two modules are disabled, the lowest
eight addresses will be functional, while the highest two will
be disabled. For example, if the shunt for Address Disable is
placed on "two" and the base switch is set to 28, the modules
will be assigned to 28, 29, 30, 31, 32, 33, 34 and 35 while
disabling the highest two positions.
NOTE:
Place unused shunts on single pin to store on board for
future use.
1
Pittway Technologica S.p.A
Via Caboto 19/3
34147 Trieste, Italy
I56-2254-01

Publicidad

loading

Resumen de contenidos para System Sensor IM-10

  • Página 1 2. All wiring to the IM-10 is done via terminal blocks. In order NOTICE: This manual should be left with the owner/user to properly make electrical connections strip approximately of this equipment.
  • Página 2 BASE ADDRESS CONNECT MODULES TO 6 7 8 9 6 7 8 9 LISTED COMPATIBLE CONTROL PANELS ONLY RESISTOR CLASS B IDC (TYPICAL) A/B SLCT COM LOSS DISABLE 1 DISABLE 2 POWER LIMITED AND SUPERVISED STATUS FROM PANEL OR INDICATORS –...
  • Página 3 DESCRIZIONE GENERALE compatibilità elettromagnetica. Il modulo per monitor a dieci ingressi IM-10 è stato progettato CABLAGGIO per l’uso in sistemi d’allarme intelligenti. Ogni ingresso NOTA: l’intero cablaggio deve essere conforme a tutte le è...
  • Página 4 NON impostare l’indirizzo più basso su un valore superiore a 90, poiché agli altri moduli verrebbero assegnati indirizzi inesistenti. 4. Per disabilitare un massimo di tre moduli non utilizzati è disponibile una derivazione. I moduli vengono disabilitati a partire da quello con l’indirizzo più alto e funzionano verso il basso.
  • Página 5: Módulo Monitor Con Diez Circuitos De Entrada

    DESCRIPCIÓN GENERAL lo sólo a un panel de control compatible. El Módulo Monitor IM-10 ha sido diseñado para su uso en un El IM-10 debe montarse en una cabina metálica conectada ade- sistema de alarma inteligente. Cada módulo sirve para inter-...
  • Página 6 Figura 1: Ejemplo de configuración típica de un circuito de iniciación NOTA: NO mezcle equipos de iniciación de alarmas de Instale los equipos de cierre de contacto incendio y de supervisión en el mismo circuito de iniciación. D500-66-00 I56-2254-01 © 2003 System Sensor...
  • Página 7 Anlagendokumentation beigefügt werden. Das IM-10-Modul sollte für die Erfüllung der EMV- ALLGEMEINES Richtlinie in einem geeigneten, geerdeten Metallgehäuse Das IM-10 Modul mit zehn überwachten Eingängen wird in intelligenten Gefahrenmeldeanlagen eingesetzt. montiert werden Jedes Modul ist als Schnittstelle zwischen der Brandmelderzentrale und externen Schließerkontakten, z.B.
  • Página 8 Adressen 28, 29, 30, 31, 32, 33, 34 und 35 zugeordnet, während die beiden höchsten Adressen abgeschaltet werden. HINWEIS: Stecken Sie nicht benutzte Steckbrücken zur Aufbewahrung auf einen einzelnen Pin auf D500-66-00 I56-2254-01 © 2003 System Sensor...