27.06.2017
3.3 Output of loop frequency
Approx. 1 sec. after calibration of the detector the loop frequency will be
displayed by pulse signals of the green LED. Firstly the 10 kHz position
of the frequency value will be indicated. For every 10 kHz frequency
value the green LED flashes once. After a break of 1 sec the 1 kHz
position is displayed in the same manner. If there is value of '0' in the 1
kHz position there will be displayed 10 flashes. The flashes for 1 kHz
position are a little bit shorter than for the 10 kHz position.
Example for 57 kHz loop frequency:
tenth values
5x 10 kHz
4
Safety information and warnings
The device should only used for the applications described by the
manufacturer.
Please keep this operation instruction always accessible and hand
it over to every user.
Inadmissible modifications to the device, use of repair parts and
supplementary equipment which are not sold or recommended by
the manufacturer can cause burning, electric shock and injuries.
Therefore the manufacturer has no liability and this excludes all
demands of warranty.
The warranty regulations of the manufacturer are valid in the
version of the purchase date for that device. There is no liability for
not suitable, wrong manual or automatic adjustments also regard-
ing no suitable applications of the device.
Repairs may only made by the manufacturer.
The power supply must be fulfill the requirements for SELV and
limited power sources according to EN 60950-1.
All connections, the start-up, maintenance, measurements and
adjustment operations to the detector have to be made from elec-
trical specialists who have special know-how in the prevention of
accidents.
For the use of devices which have contact to electrical power,
please pay attention to the valid security instructions and all pre-
vention orders of fire and accidents.
The user is responsible for an installation, which has conformity to
all technical rules in the country where the device is mounted, and
also to all regional valid orders. For that the dimension of cabling,
fuse protection, connection to ground, switch off, disconnection,
isolation controlling and the protection for overload current have to
be regarded in detail.
The detector can not be used as a security device regarding to the
security instructions of electrical machines. Using in systems with
high danger potential it is necessary to include additional protection
devices!
All work on the device must be carried out in accordance with the
national electrical codes and regional regulations.
VEK M1H_DE_GB_FR_NL_IT_ES_CE_FAAC_1.docx
single values
1 sec
7x 1 kHz
5
Technical data
Dimensions
79 x 22,5 x 90 mm (h x w x d without plug)
Protection class
IP 20
24 V AC/DC 10 % max.1,5 W SELV
Power supply
Operating tempera-
-20 °C to +70 °C
ture
Storing
tempera-
-20 °C to +70 °C
ture
Humidity
max. 95 % not condensing
Loop inductivity
25-800 µH, recommended 100-300 uH
Frequency range
25-130 kHz in 2 steps
Sensitivity
0,01 % up to 0,65 % (f/f) in 4 steps
0,02 % up to 1,3 % (L/L)
Hold time
5 minutes or infinite
Loop lead length
max. 250 m
Loop resistance
max. 20 Ohm (incl. loop lead)
Relays
250 mA / 24 V AC/DC (min. 1 mA/5 V)
presence relay
contact n.c. (adjust. operation principle)
pulse relay
contact n.o.
Signal duration
> 200 ms
Cycle time
40 ms (reaction time 80 ms)
Connections
screw terminals (power supply, relays)
binder plug (loop connection)
6
Connections
0V / GND
sensitivity
hold time
relay operation principle
frequency high
frequency low
presence signal
The information in this instruction can be changed without previous
announcement.
With this description all previous issues lose their validity.
The summary of information in this description was done with all possi-
ble acknowledge and by the best conscience.
FEIG ELECTRONIC can't give guaranty for the correctness of all
information. Particularly there is no liability by FEIG ELECTRONIC for
damages which result from a wrong installation of the device.
In spite of all efforts to correctness we are very thankful for every point
to a mistake in this description.
The installation recommendations in this description are based on
optimum conditions. For wrong environment conditions
FEIG ELECTRONIC doesn't give a warranty to optimum operation of
the detector.
You can dowload the EC declaration of conformity and other important
documents from www.feig.de.
Copyright 2017 by FEIG ELECTRONIC GmbH
5 | 19
24V =/~
0V
24V
28
s
h
5'/oo
r
/
VEK M1H
16
15
25
pulse signal
Note