LEGRAND 0 626 03 Manual De Instrucciones página 4

Répéteur pour baes sati adressables
Ocultar thumbs Ver también para 0 626 03:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 3
Repeater for addressable self-testing emergency lighting units
0 626 03
Operation
Repeater 0 626 03 should be used for installations comprising more than 250 addressable self-contained emer-
gency lighting units with one central panel 0 626 00 or 0 625 15 or another repeater, or when the longest line
exceeds 700 metres.
This repeater can also be used to separate emergency lighting in different parts of a building that have different
operating conditions.
In the event of a mains failure, the repeater continues to transmit the switching on and off orders.
For more detailed information, please consult the «Installation guide for addressable self-testing emergency
lighting units».
Input for external remote control
Description
Technical characteristics
Power supply : 230 V 50/60 Hz 20 mA
Terminal capacity : 2 x 1.5 mm
Fixing on omega rail
Width : 6 modules (105 mm)
Wiring
Consult the «Installation guide for addressable self-testing emergency lighting units».
Maintenance
Signal
Green LED off
Yellow LED on
Battery replacement ( see page 8 )
(selective area standby)
2
1
230 V~
50Hz
20 mA
Remote control output
(emergency lighting units)
2
3
Causes
1 - absence of mains supply
2 - battery dead
3 - battery disconnected
Mains presence on the remote
control line
230 VAC
N
L
A+
B–
A+
B–
F1
OUT
IN
(central panel or emergency lighting unit)
Ni-Cd 9 V or Ni-MH battery
Class II
F1: 0.5 A fuse (remote control input)
F2: 0.5 A fuse (remote control output)
1 - connect the power
2 - replace the battery
3 - reconnect the battery
Check the cable and replace the fuse(s)
4
F2
Remote control input
Consequences / solutions

Publicidad

Tabla de contenido
loading

Tabla de contenido