IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
Risk of Fire or Electric Shock
WARNING
• For Indoor /Outdoor use.
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Installation and service to be performed by a qualified licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 50,000 rms symmetrical amperes.
• For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the UL514B (standard for fitting
conduit and outlet boxes) are to be used..
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
• This unit contains no serviceable parts.
• This product does not protect against direct lightning strikes.
Type 1 installation:
A typical installation of a type 1 SPD will be connected between the secondary of the service transformer and the line side of the service
panel. This installation is intended to be installed without overcurrent protection to the SPD.
1. Determine location:
• Ensure conductor lengths are as short and straight as possible for best performance. Do not coil excess wire. The SPD functions
best if all bends in wires are rounded, ideally to a 4" radius. Hard 90 degree bend will reduce efficiency. Cut all leads to the correct
length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be mounted outside.
2. Connect wires as shown in figure 1.
3. Ensure all mounting and connections are correct and secure. Once energized the green indicator LED will be ON and visible through
the cover of the SPD.
Type 2 installation:
A typical installation of a type 2 SPD will be connected to the load side of the service panel and is intended to be installed with overcurrent
protection to the SPD.
1. Determining location:
• Ensure conductor lengths are as short and straight as possible for best performance. Do not coil excess wire. The SPD functions
best if all bends in wires are rounded, ideally to a 4" radius. Hard 90 degree bend will reduce efficiency. Cut all leads to the correct
length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be mounted outside.
• IG1240FMP33 is also available for flush mount applications.
2. Connect the green wire from the SPD to the ground bus in the panel.
• Connection may also be made to the neutral/ground bus bar if panel does not have a separate ground bus bar.
3. Connect the white wire from the SPD to the neutral bus bar in the panel as shown in figure 2.
4. Connect the two black wires to a circuit breaker as shown in figure 2. For best performance from SPD the maximum recommended
circuit breaker size of 240 V, 20 A, 2-pole should be used.
5. Ensure all mounting and electrical connections are correct and securely fastened. Once energized the green indicator LED will be ON
and visible through the cover of the SPD.
Maintenance:
AC Voltage SPD:
• Periodically check SPD to ensure green indicator LED is ON. If green LED is OFF, protection has diminished and the SPD should be
replaced immediately.
Line
240 V
Line
120 V
120 V
120 V
Neutral
Ground
Figure 1
Type 1 Installation
Type 1 or Type 2 Surge Protection Device (SPD)
BLACK
120 V
BLACK
WHITE
GREEN
INSTALLATION INSTRUCTIONS
Model IG1240RC3
Main Breaker
2-Pole, 20 A circuit
breaker shown
A=Black (Line)
B=Black (Line)
C=Neutral (White)
D=Green (Ground)
Figure 2
Type 2 Installation

Publicidad

loading

Resumen de contenidos para Intermatic IG1240RC3

  • Página 1 INSTALLATION INSTRUCTIONS Model IG1240RC3 Type 1 or Type 2 Surge Protection Device (SPD) IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS Risk of Fire or Electric Shock WARNING • For Indoor /Outdoor use. • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
  • Página 2 (2) What is Not Covered By This Warranty Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the Product, (b) damage caused by use of the Product for...
  • Página 3 INSTRUCTIONS D’INSTALLATION Modèle IG1240RC3 Limiteur de surtension de type 1 ou de type 2 INSTRUCTIONS DE SÉCURITÉ IMPORTANTES • CONSERVER CES INSTRUCTIONS AVERTISSEMENT Risque d’incendie ou de choc électrique • Pour utilisation intérieure / extérieure. • Débrancher l’alimentation au niveau des disjoncteurs ou des sectionneurs avant de procéder à l’installation ou à l’entretien.
  • Página 4 (B) Réparation ou remboursement pour les dommages au matériel correctement raccordé En plus de la garantie décrite ci-dessus, Intermatic offre à l’acheteur initial du Produit, pendant une période de cinq ans à compter de la date d’achat, les garanties suivantes : Dans l’éventualité...
  • Página 5: Riesgo De Incendio O Descarga Eléctrica

    INSTRUCCIONES DE INSTALACIÓN Modelo IG1240RC3 Dispositivo de protección contra sobretensión (SPD) tipo 1 o tipo 2 INSTRUCCIONES IMPORTANTES DE SEGURIDAD • GUARDE ESTAS INSTRUCCIONES ADVERTENCIA Riesgo de incendio o descarga eléctrica • Para instalación en interiores y exteriores. • Desconecte la energía desde los disyuntores o los interruptores de desconexión antes de realizar la instalación o el mantenimiento.
  • Página 6 (B) Reparación o reembolso por daños a equipos conectados adecuadamente Además de la garantía del Producto descrita anteriormente, Intermatic garantiza lo siguiente al comprador original del Producto por un período de cinco años a partir de la fecha de compra: En caso de que cualquier equipo eléctrico doméstico básico conectado (como se definen a continuación) presente daños (el “Equipo dañado”) como resultado directo de que un Producto...