WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Confirm Smart Guard ™ is rated for the correct voltage per part number specified on your SPD enclosure.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Installation and service to be performed by a qualified licensed technician or electrician.
• For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the UL514B (standard for fitting conduit
and outlet boxes) are to be used.
• Bonding between conduit connections is not automatic and must be provided as part of the installation.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
APPLICATION NOTES
1.
Thoroughly read instructions before installing SPD unit.
2.
This product is designed to protect against momentary transient overvoltage events.
3.
This product may not protect against nearby lightning strikes.
4.
This device features internal protection that will disconnect the surge protective component at the end of its useful life but will maintain power to the load-now unprotected. If this situation is undesirable
for the application, follow the manufacturers instructions for replacing IModule™ units.
5.
Observe warnings and instructions on front panel and unit label of product.
DEFINITIONS
Type 2 SPD: A typical type 2 SPD installation will be connected to the load side of the service panel and is intended to be installed with overcurrent protection to the SPD.
INSTALLATION:
1. Verify system voltage.
2. Make sure SPD is correctly rated for your system.
3. Determine mounting location of SPD unit.
The SPD unit should be located as close as possible to the load to be protected.
4. Mount enclosure
- Remove dead front from SPD unit.
- Disconnect power to SPD unit at power source before installation.
- Remove needed knockout from SPD unit once wire routing has been determined.
- Only one conduit connection may be made to the SPD enclosure.
- Mount enclosure using suitable fasteners in locations shown below. Do not rely on conduit fitting to support SPD unit.
5. Follow wiring diagram for all connections. (located within instruction sheets and SPD unit).
- Lead lengths can be replaced at terminal; splicing of leads is not recommended.
- Cut all wires to a minimum suitable length while maintaining a 4" recommended bend radius.
- Do not coil excess wire.
- Make sure all connections are secure.
- Replace dead front.
6. Energize SPD unit
- Flip circuit breaker to ON position at service panel or disconnect switch(es).
- Indicators: Each IModule™ has a blue LED to indicate the SPD unit has power and a green LED to indicate that the IModule™ is providing protection.
*2 Pole 30 A circuit breaker in Service Panel.
*C/B
Line (black)
Neutral (white)
Line (black)
GND (green)
SPD TYPE 2 WIRING DIAGRAM
120/240 VAC SINGLE-PHASE
SERVICING INSTRUCTIONS:
The IModule™ units will absorb the energy of the surges to protect the connected load. If the green LED is OFF, the IModule™ is no longer providing protection and should be replaced as soon as possible.
All three of the removable IModule™ units must be replaced every three years to maintain the connected equipment warranty.
TO REPLACE IModule™ UNITS:
1.
POWER MUST BE REMOVED FROM THE IModule™ BEFORE REPLACING.
2.
Disconnect power to SPD unit at service panel and/or disconnect switch(es) before servicing.
3.
Remove IModule™ to be replaced by firmly pulling straight out from SPD unit. The module door within the unit will close once the IModule™ is removed.
Make sure IModule™ is correctly rated for system.
4.
5.
Place new IModule™ back into SPD unit. Make sure IModule™ alignment key is oriented correctly when inserting.
Make sure the IModule™ is fully seated.
6.
7.
Re-energize SPD unit.
8.
Verify the blue and green LED's within each IModule™ are lit.
INSTALLATION INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
SPD
Blue LED: Power indicator
Green LED: Status indicator
ON: Protection is being provided.
OFF: IModule™ is no longer providing
protection. Replace IModule™ as soon
as possible.
Main Breaker
2-Pole, 30A circuit
breaker
Black (Line)
Black (Line)
SPD
UNIT
Neutral (White)
Green (Ground)
Type 2 Installation
IG2240-PK
TYPE 2 SURGE PROTECTIVE DEVICES
IModule™
Alignment key of module
8 1/2"
1 5/8"
3 1/4"
Plastic outdoor enclosure

Publicidad

loading

Resumen de contenidos para Intermatic SMART GUARD IG2240-PK

  • Página 1 IG2240-PK TYPE 2 SURGE PROTECTIVE DEVICES INSTALLATION INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS WARNING Risk of Fire or Electric Shock • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing. • Confirm Smart Guard ™ is rated for the correct voltage per part number specified on your SPD enclosure. •...
  • Página 2 (2) What is Not Covered By This Warranty Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the Product, (b) damage caused by use of the Product for...
  • Página 3 IG2240-PK DISPOSITIFS DE PROTECTION CONTRE LES SURTENSIONS DE TYPE 2 INSTRUCTIONS D'INSTALLATION CONSIGNES DE SÉCURITÉ IMPORTANTES • VEUILLEZ CONSERVER LE PRÉSENT MANUEL D'INSTRUCTION AVERTISSEMENT Risque d’incendie et d’électrocution • Déconnectez les disjoncteurs de l'alimentation ou éteignez les interrupteurs avant toute installation ou toute intervention. •...
  • Página 4 être utilisés conformément aux instructions qui les accompagnent, et il incombe exclusivement à l’acheteur de choisir un modèle de Produit dont les caractéristiques conviennent aux appareils à protéger. Intermatic déterminera, à son entière discrétion, si un Produit renvoyé par un acheteur a été utilisé conformément à ses instructions, si le modèle est adapté à l’usage souhaité par l’acheteur, et si le Produit est défectueux.
  • Página 5: Riesgo De Incendio O Descarga Eléctrica

    IG2240-PK DISPOSITIVOS DE PROTECCIÓN CONTRA SOBRETENSIÓN TIPO 2 INSTRUCCIONES DE INSTALACIÓN INSTRUCCIONES DE SEGURIDAD IMPORTANTES • GUARDE ESTAS INSTRUCCIONES ADVERTENCIA Riesgo de incendio o descarga eléctrica • Desconecte la alimentación de los disyuntores o interruptores de desconexión antes de comenzar la instalación o el mantenimiento. •...
  • Página 6 Producto y es de exclusiva responsabilidad del comprador elegir un modelo del Producto con las especificaciones apropiadas para el equipo que se va a proteger. Intermatic determinará, a su entera discreción, si el comprador usó el Producto devuelto según las instrucciones, si es un modelo apropiado para el uso que le da el comprador o si el Producto está...

Este manual también es adecuado para:

Smartguard ig2240-imskSmartguard serie