Use the table below to solve minor problems.
Problem
Possible Cause
No LED display on the
Low battery.
front panel.
Battery fault.
The UPS is not turned on.
Alarm continuously
The UPS is overload.
sounds when the
mains is normal.
When power fails,
The UPS is overload.
back-up time is
Battery voltage is too low.
shorten.
Battery defect. It might be
due to high temperature
operation environment, or
improper operation to battery.
The mains is normal
Power cord is loose.
but LED is flashing.
7 Specifications
Model
450
CAPACITY
450 VA / 240 W
INPUT
Voltage
Voltage Range
OUTPUT
Voltage Regulation
Transfer Time
Waveform
BATTERY
Type & Number
12 V/4.5 AH x 1
Charging Time
PHYSICAL
Dimension (DxWxH)
Net Weight (kgs)
3.55
Environment
0-90 % RH @ 0-40° C (non-condensing)
Humidity
Noise Level
MANAGEMENT
USB/RS-232 (Option)
Supports Windows 98 SE/ME/NT 4.x/2000/2003/XP/Vista/2008
Solutions
Charge the UPS at least 6 hours.
Replace the battery with the same
type of battery.
Press the power switch again to turn
on the UPS.
Remove some loads first. Before
reconnecting equipment, please
verify that the load matches the UPS
capability specified in the specs.
Remove some critical load.
Charge the UPS at least 6 hours.
Replace the battery with the same
type of battery.
Reconnect the power cord properly.
650
850
650 VA / 360 W
850 VA /480 W
110/120 VAC or 220/230/240 VAC
81-145 VAC / 162-290 VAC
+/-10%
Typical 2-6 ms, 10 ms max.
Simulated Sine Wave
12 V/7 AH x 1
12 V/9 AH x 1
4-6 hours recover to 90% capacity
287 x 100 x 142 mm
4.25
4.9
Less than 40 dB
Line Interactive UPS
1. Lieferumfang
Im Lieferumfang sollten Sie folgendes finden:
- UPS Einheit
- Schnell Installationsanleitung
- Kommunikationskabel ( nur für USB/RS-232 port Modell)
- Stromkabel ( nur für IEC-input Modell)
2. Produktübersicht
Vorderansicht:
Netzschalter
UPS status LED
AC Modus: leuchtet grün
Batterie Modus: blinkt grün
Rückansicht:
Schuko Type I
IEC Type
Quick Guide V. 1.1
GE
Ausgabe Anschluss
AC Input
Schutzschalter
Optionen
USB com. port
Modem / Telefon /
Netzwerk
Überspannungsschutz
RS-232 com. Port

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Interactive 450Interactive 650Interactive 850

Tabla de contenido