MCS5-115-230/24
Art. No. 85061
OPERATING INSTRUCTIONS
product of the
series
1
+
5
OUTPUT
2
-
DC24V/5A
4
Uout ADJ. 24-28 V
3
Uout OK
OFF
AUTORESTART
4
ON
SWITCH MODE POWER SUPPLY
ART. NO. 85061
3
L
INPUT
5
100-240VAC
2
N
1
54
115
50
AC115-230V
5
L
4
N
Art. Nr. 85061
L
5
4
N
11
Art. Nr. 85061
AC115-230V
L
5
4
N
Art. Nr. 85061
L
5
4
N
12
Art. Nr. 85061
IND.CONT.EQ
E196712
66PN
(1) General
This unit employs many features previously unavailable in an industrial power supply. It has been
designed to withstand the high levels of interference found in heavy industry and has emission
levels low enough for it to be used in residential, commercial and light industrial environments.
The MCS5-115-230/24 has a high level of reserve power. This enables loads with significant inrush
current to be supported and will also ensure that circuit breakers will trip in event of short circuit.
A protective feature is provided which will take control as the unit approaches the power limit due
the overload or excessive temperature brought about by lack of ventilation.
In order to take the best advantage of the
features that this power supply has to offer
and to ensure long term reliability for your
equipment, please read these instructions
carefully before installation and use. They
should be retained for future reference.
6
7
8
6
0
1
2
3
4
5
(2) Technical specification, Art. No. 85061
Nominal voltage
Input voltage range
Input current, I
nom.
Inrush current
Efficiency, typ.
Power factor, typ.
External fuse max. 10 A
Safety class
Output voltage, adjustable 24 - 28 VDC
Static regulation accuracy
Dynamic regulation accuracy typ.
Start up time
Holdup time of the output, typ.
Output current, continuous +60°C
Output current, continuous +40°C (110 - 265 VAC)
Output current, short circuit , max. 300 ms
Output ripple
Overloading / temperature protection
Overvoltage shutdown, when auto restart = OFF
Overcurrent shutdown (breaking off)
Relative humidity
Operation temperature
Storage temperature
Protection class, case , EN 60529
Dimensions W x H x D; Weight
(3) Features
[1] Output terminal:
Conductor sizes
Solid
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded with ferrule without / with plastic sleeve 1,5 mm² / 16 AWG
Ferrule minimum lenght must be
Tightening torque:
[2] Output voltage adjust 24 - 28 VDC
9
[3] Output voltage "OK"
[4] Autorestart ON / OFF selection with jumper. Change is only allowed after 5 minutes of
disconnection from the mains. Use flat nose pliers to change the position. "OFF" means
shut down by over current or overvoltage or over temperature. Reset by disconnecting the
mains for 2 min. "ON" means continuous pulsated restart operation instead of shut down
(factory default).
[5] Input terminal:
Conductor sizes
6
Solid
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded
1,5 - 2,5 mm² / 16 - 14 AWG
Stranded with ferrule without / with plastic sleeve 1,5 mm² / 16 AWG
10
Ferrule minimum lenght must be
Tightening torque:
(4) Location
The power supply is cooled by natural convection. It is important to maintain clearance to other
components as much as possible to ensure best performance and long term stability. Top and
bottom clearances should be 100 mm at minimum. Side clearance to other equipment should
be 50 mm or >100 mm if that equipment is heat generating. The ambient temperature should be
measured on the underside of the unit. There will be an increase of 25°C at the top. If natural
convection is restricted, forced cooling should be used. Mounting should comply with EN
60950-1 point 4.7 and 4.6.1. Protection class of the case IP20 (EN 60529).
(5) Mounting [8]
The rail should be fixed solidly so that it cannot twist when mounting or removing the unit.
Mounting instructions [6], Removing instructions [7].
(6) Switching on
Factory set, ready to use, check the connection diagrams for parallel and series connection.
(7) Loading capacity
The nominal current is 5 A but due to the nature of industrial loading, the power supply has been
designed to support loads with high inrush currents without damage or shutdown. Curve [9]
shows the typical voltage / current curve. Decreasing part of the curve [9] shows the current
limitation. Curve [10] shows the typical overload / temperature limit. To ensure correct
convection cooling, the unit must always be mounted with rail horizontally.
(8) Parallel connection [11]
Up to 5 units may be connected in parallel. The open circuit voltage of each unit should be set
to same value. Accuracy of setting will determine how well the units share the load current. The
gauge and lenght of the cable between each power supply and the common point should be the
same. Units should only be used in parallel where the supply exceed 110 volts.
(9) Series connection
Up to 2 units may be connected in series to give either 48 VDC or +/-24 VDC. Check the
connection diagram [12].
(10) Using circuit breakers on the power supply output:
On the short circuit, the power supply will trip, for example, the following ABB-STOTZ circuit
breaker:
(11) Standards
Electrical safety
EMC
Immunity
Emissions
We reserve the right to change this specification.
100 - 240 VAC 50/60 Hz
90 - 265 VAC 50/60 Hz
1,4 A
/100 VAC - 0,6 A
rms
< 25 A / 230 VAC after 1 ms
83% / 115 VAC, 87% / 230 VAC
(UL listed Bussmann Typ. AGC-10A or
Littelfuse No. 314 010) or ABB S201-B10A
0->100%, 5% 1ms / 100%->5%, 5% 1ms
< 4 s / 100 VAC - < 3 s / 240 VAC
5 - 95% , no condensing
54 x 115 x 151 mm; 0,75 kg
≥ 10 mm
0,4 - 0,5 Nm / 5 - 7 lb. in.
≥ 10 mm
0,4 - 0,5 Nm / 5 - 7 lb. in.
S201-Z1,6A
EN 60950-1, UL 1950, UL 508, SELV
EN 61204-3, (2000), Emissions, Immunity
EN 61000-4-2 (1995) ESD 4/8 kV
EN 61000-4-3 (1996) Rf-field 10 V/m
EN 61000-4-4 (1995) EFT/B 2/2 kV
EN 61000-4-5 (1995), Surge 1/2 kV; 500 V
EN 61000-4-6 (1996) Cond. Rf 10 V
EN 61000-4-8, (30 A/m)
EN 61000-4-11
ENV 50204 (1995) Rf-field 10 V/m
EN 55022 B, RF-emissions
EN 61000-3-2 ,class A
EN 60204-1, 60 V / 1 s
V1.4
/230 VAC
rms
> 0,95
1
24 VDC
+/-1%
> 18 ms / 230 VAC
5 A
6 A
> 10 A
< 20 mV
rms
Yes
> 28,5 VDC
> 6,2 A
typ.
0°C - +60°C
-25°C - +85°C
IP20