meibes MHK 25 Información Técnica Para El Montaje Y El Funcionamiento página 18

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

2. Boiler guard
Boiler guard (DN 50-200)
Housing: welded round vessel with connecting pieces of seamless steel pipe incl. Victaulic nut. A cleaning opening with
a 1" drain ball valve is located in the base. The two ¾" sleeve sockets in the base are for installing magnetite separators
(optional) and are closed with plugs on delivery. An automatic floating air vent, a flushing ball valve and a thermowell for
holding a temperature sensor are fitted to the lid. The height of the boiler guard can be adjusted by sawing through the
pipe. The insulation is made from EPP .
Max. permissible pressure rating: PN 6 / PN 10
Max. permissible temperature: 110 °C
floating air vent
Settling chamber
Deflector plate
Venting channel
Full insulation
incl. connections/
Victaulic unions
Up to 2 optional
magnet cartridges
18
Automatic
Rinsing valve with
hose fitting
Thermowell for
temperature sensor
Flow straightener
Perforated plates
Separation plates
Sludge pan
Drainage ball valve
with hose fitting
Height-adjustable
foot

Publicidad

Tabla de contenido
loading

Tabla de contenido