Input & Output Connections - Cablematic OPTIMA-T09W-06K-230V Manual De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4. INSTALACION: UPS INDIVIDUAL – REGLETAS DE CONEXIÓN
AC LINES: CONNECTION IN UPS TERMINAL BLOCK
Make sure the UPS is Off before starting the installation.
Remember to check all wires to be connected are not powered (including external batteries).
TERMINAL BLOCK PREPARATION
Remove TB cover located on rear side of UPS.
Do not connect UPS to a wall socket. Usually wall sockets provide 3KVA maximum. AC lines must be connected to electrical board using
cables with required gauge.
INPUT & OUTPUT CONNECTIONS
First of all, connect ground terminals to system earth. Ground must always be first terminals to connect and last to disconnect.
Connect input and output cables in terminals of the TB located on rear panel of UPS. Please make connections following below drawings
according to your model.
IMPORTANT: In case of differences between below figures and information printed on the UPS you must follow information printed
on UPS.
OPTIMA 6K/10K 230
UPS with direct output from inverter
This model has 1phase input 220Vac
Output is 1phase selectable between: 208, 220, 230 or 240Vac
USER MANUAL - OPTIMA T09W 6K/10K
VER.1801.25-WP+ (ENG)
11

Publicidad

Tabla de contenido
loading

Tabla de contenido