3.
Specifications
Basic composition
Type of measurement
Measurement range
Dynamic range
Output signal
Linearity over the entire measurement range
and
within the operating temperature limits indi-
cated
4-20mA output scale factor
GAP + BNC scale output factor
GAP + BNC centre scale output
GAP + BNC scale start output
GAP + BNC scale end output
Sensitivity to temperature
Power supply
Operating range
Sensor connection
Output connections
Transmitter weight
Sensor weight
Maintenance
Special versions
sensor, extension, transmitter
differential
± 1 mm (0,5÷2,5 mm)
frequency 0÷500 Hz (displace-
ments)
frequency 1.5÷10.000 Hz (vibra-
tions)
4-20mA loop + analogue gap
± 1%
according to order code
100 mV/mil (3.94 mV/µm)
5.00VDC
1.07VDC
8.94VDC
according to ANSI/API 670-93
24VDC nominal
temperature (sensor)
temperature (transmitter)
humidity (sensor)
humidity (transmitter)
miniature coaxial connector
(sensor / transmitter)
4-way screw terminal board
(transmitter / instrument)
BNC for analyser connection
~ 1 Kg
~ 0,1 Kg
none
ATEX certified version
for applications in classified areas
II 1 G Ex ia IIC T5 Ga
II 1 G Ex ia IIC T6 Ga
= - 35 to + 175° C
= - 20 to + 70° C
= max 100%
= max 95% (non conden-
sing)
5