P4 on the display, the device is set to the high speed stop force for the
»
Motor2. There are optional values from 0 to 20. After choosing the value,
press the FUN button to save the data. (factory setting is 10).
3. Setting the high speed running time (P5) :
There are optional levels 0 - 33s. "0" indicates operation without high speed,
the opening will continue to operate at low speed. The maximum value is 33s.
After choosing the value, press the FUN button to save the data (factory
setting on 5s).
4. Setting the auto close time after swiping the card (P6)
(NOTE! This automatic closing time only means the automatic closing
function that is performed through the external device). There are optional
levels 0 - 99s. "0" means the gate will not close automatically after reading
the card. The maximum automatic closing time after reading the card is 99s.
After choosing the value, press the FUN button to save the data (factory
setting 10s).
5. Setting the time interval for opening and closing
P7 on the display, indicates the time setting for opening. There are
»
optional levels 0 - 10s. "0" means that the double s open simultaneously.
"1" means that Motor1 begins to open 1 second before Motor2 begins
to open. The maximum value of the opening time interval is 10s. After
choosing the value, press the FUN button to save the data (factory
setting 0s).
P8 on the display, indicates the setting of the closing time. There are
»
optional levels 0 - 10s. "0" means that the double s close simultaneously.
"1" means that Motor 2 starts to close with 1 second before Motor 1 starts
to close. The maximum value of the closing time is 10s. After choosing
the value, press the FUN button to save the data (factory setting 0s).
6. Setting the automatic closing time (P9)
There are optional levels 0 - 99s. "0" means that the gates do not close
automatically. After choosing the value, press the FUN button to save
(factory setting 0s).
7. Setting the lamp/alarm output control (PA)
There are optional levels 0 - 3. "0" - alarm in a monostable way, the lamp
15