Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

HUMIDITY SENSING
FAN / FLUORESCENT LIGHT / NIGHT LIGHT
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OB-
SERVE THE FOLLOWING:
1. Use this unit only in the manner intended
by the manufacturer. If you have questions,
contact the manufacturer at the address or
telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch
power off at service panel and lock the ser-
vice disconnecting means to prevent power
from being switched on accidentally. When
the service disconnecting means cannot be
locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be
done by a qualified person(s) in accordance
with all applicable codes and standards,
including fire-rated construction codes and
standards.
4. Sufficient air is needed for proper combustion
and exhausting of gases through the flue
(chimney) of fuel burning equipment to pre-
vent backdrafting. Follow the heating equip-
ment manufacturer's guideline and safety
standards such as those published by the
National Fire Protection Association (NFPA),
and the American Society for Heating, Re-
frigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden
utilities.
6. Ducted fans must always be vented to the
outdoors.
7. Acceptable for use over a tub or shower when
connected to a GFCI (Ground Fault Circuit
Interrupter) - protected branch circuit.
8. This unit must be grounded.
CAUTION
1. For general ventilating use only. Do not use
to exhaust hazardous or explosive materials
and vapors.
2. This product is designed for installation in
flat ceilings only. DO NOT MOUNT THIS
PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy
and/or unbalanced impellers, keep drywall
spray, construction dust, etc. off power unit.
4. Please read specification label on product for
further information and requirements.
Installer: Leave this manual
with the homeowner.
To register this product visit:
www.nutone.com
OPERATION
The humidity control and fan can be
oper-ated separately. Use a 1- or 2-func-
tion wall control. Do not use a dimmer
switch to operate the humidity control or
light. See "Connect Wiring" for details.
SENSOR OPERATION
This humidity-sensing
fan responds to:
(a) rapid to moderate humidity increases
and (b) humidity above a 50%-100% rela-
tive humidity set-point. (a) and (b) are set
with "SENSITIVITY" adjustment. Fan may
occasionally turn on when environ-mental
conditions change. If the fan contin-uously
responds to changing environ-mental condi-
tions, "SENSITIVITY" adjust-ment may be
required (see section below).
STATUS INDICATOR
This indicator can only be seen by looking
directly at it. Normal mode is 5-seconds on
and off. If it blinks rapidly for 5-seconds and
then off, check sensor connections on grille
and fan housing.
MANUAL ON WITH TIMED OFF
For odor or vapor control, the fan can be en-
ergized by cycling its wall-mounted switch
if one is installed. Once the fan has been
turned on in this manner, it will remain on
for the set "TIMER" period.
To manually energize the fan:
1. Go to Step 2 if switch is already on;
otherwise, turn switch on for more than
1 second.
2. Switch off for less than 1 second.
3. Switch back on and fan will turn on.
SENSITIVITY ADJUSTMENT
"SENSITIVITY" has been factory set for
most shower applications. If the fan is in a
tub area or is used for dampness control,
the "SENSITIVITY" may need to be in-
creased toward maximum ("MAX."). If the
control is responding too often to changing
environmental conditions, adjustment to-
ward less ("MIN.") "SENSITIVITY" may be
required. To adjust the "SENSITIVITY":
1. Turn power off at electrical service
panel.
2. T h r o u g h t h e g r i l l e , l o c a t e t h e
"SENSITIVITY" screwdriver slot.
3. Using a small, flat-blade screwdriver,
carefully rotate "SENSITIVITY" adjust-
ment toward "MAX." or "MIN."
4. Turn power on and check operation
by turning on shower or other humidity
source until fan turns on.
5. Repeat above steps if necessary.
MODEL QTXEN110SFLT
TIMER ADJUSTMENT
This humidity-sensing fan has a "TIMER". It
is user-adjustable from 5 to 60 minutes and
is factory-set at 20 minutes. The "TIMER"
controls how long the fan remains on (a)
after rise in humidity and (b) humidity level
are both below the user-adjustable "SEN-
SITIVITY" setting or after being energized
by cycling power switch.
To adjust the "TIMER":
1. Disconnect power at electrical service
panel.
2. Through the grille, locate the "TIMER"
screwdriver slot.
3. Using a small, flat-blade screwdriver,
carefully rotate "TIMER" adjustment to
desired setting (5 to 60 minutes).
4. Check operation by cycling power
switch as instructed under "MANUAL
ON WITH TIMED OFF" or by turning on
a humidity source until fan turns on.
5. Check "TIMER" setting with watch or
clock after turning humidity source off
if it was turned on it Step 4.
6. Repeat above steps if necessary.
CLEANING &
MAINTENANCE
For quiet and efficient operation, long life,
and attractive appearance - lower or remove
grille and vacuum interior of unit with the
dusting brush attachment.
The motor is permanently lubricated and
never needs oiling. If the motor bearings are
making excessive or unusual noises, replace
the motor with the exact service motor. The
impeller should also be replaced.
SENSOR CLEANING
The humidity sensor is mounted in the grille.
The sensor will operate most reliably when
cleaned occasionally as follows:
1. Disconnect power at service entrance.
2. Remove the grille. Use a dry dustcloth,
clean toothbrush, or lightly vacuum to
clean sensor and grille. DO NOT USE
ABRASIVE CLOTH, STEEL WOOL
PADS, OR SCOURING POWDERS.
3. DO NOT USE cleaning sprays, solvents,
or water on or near the sensor!
Page 

Publicidad

Tabla de contenido
loading

Resumen de contenidos para NuTone QTXEN110SFLT

  • Página 1 MODEL QTXEN110SFLT HUMIDITY SENSING Page  To register this product visit: www.nutone.com FAN / FLUORESCENT LIGHT / NIGHT LIGHT READ AND SAVE THESE INSTRUCTIONS WARNING OPERATION TO REDUCE THE RISK OF FIRE, ELECTRIC TIMER ADJUSTMENT The humidity control and fan can be SHOCK, OR INJURY TO PERSONS, OB- oper-ated separately.
  • Página 2: Typical Installations

    MODEL QTXEN110SFLT Page  TYPICAL INSTALLATIONS • Locate unit above (GFCI protected circuit required) or within 5 feet of shower head. • Locate unit away from heating or cooling sources which can affect humidity levels. • Do not locate near window. Unit may respond to the outdoor humidity level. • Unit must be installed in ceiling to properly sense moisture. • Locate unit only on flat ceilings up to 12 feet high for proper sensing.
  • Página 3 MODEL QTXEN110SFLT Page  1b. Mount housing anywhere between 2. Attach damper/ trusses, joists, or I-joists using hanger duct connector. bars. Snap damper / duct con- nector onto housing. Make sure connector is flush Sliding hanger bars are provided to allow for accurate posi- with top of housing and tioning of housing anywhere between framing. They can be damper flap falls closed. used on all types of framing (I-joist, standard joist, and truss construction) and span up to 24”.
  • Página 4: Service Parts

    TICULAR PURPOSE. 97017084 Motor Plate & Control Assembly * During this three-year period, NuTone will, at its option, repair or replace, without charge, any product 99250959 Washer #8 (4 req’d) or part which is found to be defective under normal use and service.
  • Página 5: Limpieza Y Mantenimiento

    MODELO QTXEN110SFLT Para registrar este producto, visite: Página  VENTILADOR CON SENSOR DE www.nutone.com HUMEDAD / LÁMPARA FLUORESCENTE / LÁMPARA DE NOCHE LEA Y CONSERVE ESTAS INSTRUCCIONES OPERATION ADVERTENCIA PARA REDUCIR EL RIESGO DE INCENDIOS, El control de humedad y el ventilador pueden AJUSTE DEL TEMPORIZADOR DESCARGAS ELÉCTRICAS O LESIONES...
  • Página 6: Instalaciones Típicas

    MODELO QTXEN110SFLT Página  INSTALACIONES TÍPICAS • C oloque la unidad sobre o dentro de una distancia de 1.5 m (5 pies) de la cabeza de la regadera (se requiere un circuito protegido con un GFCI). • U bique la unidad lejos de fuentes de calefacción o enfriamiento que puedan afectar los niveles de humedad. • No la ponga cerca de una ventana. La unidad puede responder a los niveles de humedad del exterior.
  • Página 7: Conexión Eléctrica

    MODELO QTXEN110SFLT Página  1b. I nstale la cubierta en cualquier parte 2. Acople el conectador entre las armaduras, viguetas o viguetas del regulador de “I” por medio de barras de suspensión. tiro/conducto. Conecte a presión el Se proporcionan barras de suspensión deslizantes para facilitar conectador del regulador de la colocación adecuada de la cubierta en cualquier parte entre la tiro/conducto en la cubierta.
  • Página 8: Piezas De Repuesto

    Tornillo de mariposa n.º 8-18 x 0.375 Para tener derecho al servicio de la garantía, usted debe (a) notificar a NuTone a la dirección y número de teléfono que aparecen abajo, (b) proporcionar el número de modelo y la identificación de la pieza y (c) describir la naturaleza de cualquier defecto en el producto o pieza.

Tabla de contenido