Descargar Imprimir esta página

Synchronization Interval - ZIV 6IRV Manual De Instrucciones

Equipo de control de interruptor

Publicidad

DNP Protocol Configuration
Relay Number
Remote Terminal Unit Address. Addresses 0xFFF0 to 0xFFFF are reserved as Broadcast
Addresses.
T Confirm Timeout
Timeout while waiting for Application Layer Confirmation. It applies to Unsolicited
messages and Class 1 and Class 2 responses with event data.
Max Retries
Number of retries of the Application Layer after timeout while waiting for Confirmation.
Enable Unsolicited
Enables or disables Unsolicited reporting.
Enable Unsol. after Restart
Enables or disables Unsolicited after Restart (for compatibility with terminals whose
revision is before DNP3-1998). It has effect only if Enable Unsolicited after
Restart is set.
Unsolic. Master No
Destination address of the Master device to which the unsolicited responses are to be sent.
Addresses 0xFFF0 to 0xFFFF are reserved as Broadcast Addresses. It is useful only when
Unsolicited Reporting is enabled.
Unsol. Grouping Time
Delay between an event being generated and the subsequent transmission of the
unsolicited message, in order to group several events in one message and to save
bandwidth.

Synchronization Interval

Max interval time between two synchronization. If no synchronizing inside interval,
indication
IIN1-4 (NEED TIME). This setting has no effect if Synchronization
Interval is zero.
DNP 3.0 Rev
Certification revision
(IED) Certification Procedure Subset Level 2 Version 2.3 29-Sept-03)
Binary Changes CLASS
Selection to send Binary Changes as CLASS 1 CLASS 2 CLASS 3 or None.
Analog Changes CLASS
Selection to send Analog Changes as CLASS 1 CLASS 2 CLASS 3 or None.
Counter Changes CLASS
Selection to send Counter Changes as CLASS 1 CLASS 2 CLASS 3 or None.
Binary Status
Send Binary with status otherwise without status
32 Bits Analog Input
Send Analog All Variations and Analog Change Event Binary Changes with 32 bits
otherwise with 16 bits
Atención
© ZIV Aplicaciones y Tecnología, S.A. Zamudio 2004
Este documento contiene información confidencial propiedad de ZIV S.A. Cualquier forma de reproducción o
divulgación está absolutamente prohibida y puede ser causa de severas medidas legales.
DNP 3.0 : Device Profiles Document
RTU Address ):
(
(N7 Confirm Timeout) :
(N7 Retries) :
(Enable Unsolicited Reporting) :
MTU Address) :
. (
(Unsolicited Delay Reporting) :
.
STANDARD ZIV or 2003 (DNP3-2003 Intelligent Electronic Device
.
.
.
.
.
60 of 84
Page
:

Hide quick links:

Publicidad

Capítulos

loading

Productos relacionados para ZIV 6IRV